8.  PROBLEMS, MAINTENANCE AND WARRANTY

8.1  Probe errors

Error

Reason

Action

E1-E1

The probe 

Pr1

 may be interrupted 

or in short circuit, or may measure a 
value outside the allowed range

Check the correct 
connection of the 
probe with the in-
strument and check 
the probe works 
correctly

E2-E2

The probe 

Pr2

 may be interrupted 

or in short circuit, or may measure a 
value outside the allowed range

----

Process measurement not available

8.2  Other errors

Error

Reason

Action

ErAt

Auto-tuning not pos-
sible because the 
process value is too 
high or too low

Press the 

 keyin order to make 

the error message disappear. 
Once the error has been found, 
try to repeat the auto-tuning

noAt

Auto-tuning not fin-
ished within 12 hours

Check the the probe and actuator 
functioning and try to repeat the 
auto-tuning

LbA

Loop control interrupt-
ed (Loop break alarm)

Check the the probe and actuator 
functioning and swap the instru-
ment to (

rEG

) control

ErEP

Possible EEPROM 
memory anomaly

Press the 

 key

In error conditions, the instrument provides the output power 
programmed with parameter 

oPE

 and activates the desired 

alarm(s), if the relative parameters 

ALni

 have been pro-

grammed as 

yES

.

8.3  Cleaning

We recommend cleaning of the instrument with a slightly 
wet cloth using water and not abrasive cleaners or solvents 
which may damage the instrument.

8.4  Warranty and Repairs

The instrument is under warranty against manufacturing 
flaws or faulty material, that are found within 18 months from 
delivery date.
The warranty is limited to repairs or to the replacement of the 
instrument.  The eventual opening of the housing, the viola-
tion of the instrument or the improper use and installation of 
the product will bring about the immediate withdrawal of the 
warranty effects.
In the event of a faulty instrument, either within the period 
of warranty, or further to its expiry, please contact our sales 
department to obtain authorisation for sending the instru-
ment to our company.  The faulty product must be shipped 
to Ascon Tecnologic with a detailed description of the faults 
found, without any fees or charge for Ascon Tecnologic, 
except in the event of different agreements.

8.5  Disposal

The appliance (or the product) must be disposed 

of separately in compliance with the local standards 

in force on waste disposal.

9.  TECHNICAL DATA

9.1  Electrical characteristics

Power supply:

 12 VAC/VDC, 24 VAC/VDC, 100 ÷ 240 VAC 

± 10%;

Frequency AC:

 50/60 Hz;

Power consumption:

 about 4 VA;

Inputs:

 2 inputs for temperature probes:  

 

NTC (103AT-2, 10 k

W

 @ 25°C) or 

 

PTC (KTY 81-121, 990

W

 @ 25°C) or 

 Pt1000 
 

+ 2 free voltage digital inputs contacts;

Outputs:

 Up to 4 relay or Vdc for SSR outputs:

EN 61810 EN 60730

UL 60730

Out1 - SPDT - 8A - 
1/2HP 250 V

8 (3) A

4 (4) A

10 A Res.

Out2 - SPDT - 8A - 
1/2HP 250 V

8 (3) A

4 (4) A

10 A Res.

Out3 - SPST-NO - 5A - 
1/10HP 125/250 V

5 (1) A

2 (1) A

2 A Gen. Use

Out4 - SPST-NO - 5A - 
1/10HP 125/250V

5 (1) A

2 (1) A

2 A Gen.Use

Relay outputs slectrical life as for EN 60730:

  

Out1, Out2: 100000 operations; Out3, Out4: 100000 operations;

Installation category:

 II;

Measurement category:

 I;

Protection class against electric shock:

  

Class II for Front panel;

Insulation:

 Reinforced insulation between the low voltage 

section (relay outputs) and the front panel; Reinforced insula-
tion between the low voltage section (relay outputs) and the 
extra low voltage section (inputs, SSR outputs); No insulation 
between power supply, inputs and SSR outputs; 50 V insula-
tion between RS485 and extra low voltage section.

9.2  Mechanical characteristics

Housing:

 Self-extinguishing plastic, UL 94 V0;

Heat and fire resistance category:

 D;

Dimensions:

 78 x 35 mm, depth 75.5 mm;

Weight:

 about 150 g;

Mounting:

 Incorporated flush in panel (pane thickness  

12 max. mm) in a 71 x 29 mm hole;

Connections:

 Fixed or removable screw terminal block for 

0.2 ÷ 2.5 mm

2

/AWG 24 ÷ 14 cables;

Protection degree:

 IP65 (NEMA 3S) when mounted with 

the optional screw type bracket;

Pollution degree:

 2;

Operating temperature:

 0 ÷ 50°C;

Operating humidity:

 < 95 RH% with no condensation;

Storage temperature:

 -10 ÷ +60°C.

Summary of Contents for K31D

Page 1: ...an therefore be used in applications that require a control for the temperature difference between 2 different environments such as liquid coolers chillers natural air conditioning systems through the air recirculation heating by solar panels or in many other applications where 2 temperature readings are needed The controller is also Index 1 Instrument description 1 1 1 General description 1 1 2 F...

Page 2: ...that the process value is lower than the one programmed for parameter AdE 12 LED Shift index Indicates that the process value is within the range SP AdE SP AdE 13 LED Shift index Indicates that the process value is higher than the one set for parameter AdE 2 PROGRAMMING 2 1 Set Point Fast Programming This procedure allows you to quickly set the active Set Point and when required the alarm threshol...

Page 3: ...r or disappear on this level by fol lowing this procedure Enter the menu ConF and select the parameter to be made programmable or not programmable in the menu oPEr Once the parameter has been selected if the LED SET is OFF this means that the parameter is programmable only in the menu ConF if instead the SET LED is ON this means that the parameter is also programmable in the menu oPEr To modify th...

Page 4: ...entioned rule must adopt all the necessary protective measures The instrument MUST NOT be used in dangerous environments flammable or explosive without adequate protection The installer must ensure that EMC rules are respected also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for fl...

Page 5: ...probe is not connected The instrument allows the measurement calibration that can be used to recalibrate the instrument according to application needs This can be done through parameters OFS1 OFS2 and rot Setting rot 1000 and oFS 1 2 it is possible to set a posi tive or negative offset that is simply added to the value read by the probe before visualisation which remains constant for all the measu...

Page 6: ...2HL the process value considered by the controller is Pr1 P2LL When P2HL and P2LL thresholds are exceeded by Pr2 tem perature a control takes place as if the Pr2 temperature is the value of the limit regardless of the value actually read The aim of this function is to limit the differential regulation to within a maximum range of the Pr2 measurement With the differential control the working mode F...

Page 7: ...gle Action PID control can be obtained by program ming parameter Cont Pid and works on 1 rEG output depend ing on the active Set Point SP the functioning mode Func and on the instrument PID algorithm with 2 freedom degrees If the Out1 analogue output is present 0 4 20 mA 0 2 10 V the output will operate as a regulation output providing a value proportional to the regulation power calculated by the...

Page 8: ...h Func CooL 4 If FAST Auto tuning is desired to start automati cally all times the Set Point is changed or at the end of the programmed Softstart cycle The Auto tuning starts anyway if PV is lower than SP SP 5 with Func HEAt or higher than SP SP 5 with Func CooL 1 If OSCILLATORY Auto tuning is desired to start auto matically all times the instrument is switched ON 2 If OSCILLATORY Auto tuning is d...

Page 9: ...d when the relative parameters are set to InF If is desired only one ramp e g to reach SP1 it is enough to program the parameter SLor with the desired value The ramp SLor will always be active at Power ON and when the Active Set Point value is changed On the contrary if an automatic cycle is to be executed at Power ON program nSP 2 then the two Set Point values SP1 and SP2 and naturally parameters...

Page 10: ...AL1 and is deactivated when thePV goes below the value AL1 HAL1 In this way is possible to program with AL1L and AL1H parameters the minimum and the maximum limits of AL1 thresholds LoAb OUT AL1 AL1 PV HAL1 time HiAb off off off OUT AL1 AL1 PV HAL1 time off off off ON ON ON ON LodE Deviation low alarm The alarm is activated when the process value goes below the value SP AL1 and is deactivated when...

Page 11: ...f a measurement error yES Alarm active no Alarm deactivated 5 12 Loop Break Alarm Function All the parameters referring to the Loop Break alarm function are contained in the group LbA The Loop Break alarm is available on all the instruments which intervenes when for any reason short circuit of a thermocouple thermocouple inversion load interruption the loop control is interrupted First of all it i...

Page 12: ...nSP 2 and when active it disables the selection of the active Set Point through the parameter SPAt and through the key 5 15 RS485 Serial Interface The instrument can be equipped with a RS485 serial com munications interface by means of which it is possible to connect the controller to a network to which other instru ments PLC controllers are connected All these devices typically depend on a Person...

Page 13: ...nfiguration or to keep a copy of the parameters setting of an instrument and allow its rapid retransmission The same device allows to connect a PC via USB with which through the appropriate configuration software for AT Univer salConf tool the operating parameters can be configured To use the A01 device it is necessary that the device or instrument are being supplied AC supply Supply adapter 12 VD...

Page 14: ...Number of decimal figures 0 1 0 12 Aot Analogue control Output type 0 20 0 20mA 4 20 4 20 mA 0 10 0 10 V 2 10 0 10 V 0 10 13 Unit Temperature unit of measurement C F C 14 FiL Input digital filter oFF Not active 0 1 20 0 s 1 0 15 oFS1 Measuring Offset Pr1 1999 9999 0 16 oFS2 Measuring Offset Pr2 1999 9999 0 17 rot Rotation of the measuruing straigìht line 0 000 2 000 1 000 18 InE oPE functioning in...

Page 15: ... 1 33 AL1d AL1 Alarm activation delay oFF Not active 1 9999 s OFF 34 AL1i Alarm AL1 activation in case of probe error no yES no Group AL2 AL2 Alarm Parameters Parameter Description Range Default Note 35 OAL2 Output where alarm AL2 is addressed oFF Not active Out1 Out2 Out3 Out4 oFF 36 PrA2 AL2 Alarm PV reference Pr1 Pr2 P1 2 P1 L Pr1 37 AL2t AL2 Alarm type LoAb Absolute Low HiAb Absolute High LHAb...

Page 16: ... error no yES no Group lba Loop Break Alarm Parameters Parameter Description Range Default Note 55 OLbA Output where LbA alarm is addressed oFF Not active Out1 Out2 Out3 Out4 OFF 56 LbAt Time necessary to activate alarm LbA oFF Not active 0 9999 s OFF Group reg Control Parameters Parameter Description Range Default Note 57 Cont Control type Pid PID on FA Asymmetrical ON OFF on FS Symmetrical ON OF...

Page 17: ...SP Active Set Point selection oFF Control in OFF mode noF 78 diSP Displayed Variable Pr1 Pr1 Value Pr2 Pr2 Value P1 2 Pr1 Pr2 Value Pou Control Power SP F Active Set Point Value SP o Operative Set Point value AL1 AL1 threshold AL2 AL2 threshold AL3 AL3 threshold P1 2 79 AdE Shift value for the shift index functioning 0 OFF 1 9999 2 80 Edit Fast programming Active Set Points and Alarms SE Set Point...

Page 18: ... contact our sales department to obtain authorisation for sending the instru ment to our company The faulty product must be shipped to Ascon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of different agreements 8 5 Disposal The appliance or the product must be disposed of separately in compliance with the local standa...

Page 19: ...61010 1 10 HOW TO ORDER Model K31D Instrument with mechanical keys a Power supply H 100 240 VAC L 24 VAC DC F 12 VAC DC b Inputs 2 For PTC NTC Thermistors or Pt1000 resistance thermometer d Output 2 Out2 R Relay SPDT 8A resistive load O Vdc for SSR Not present e Output 3 Out3 R Relay SPST NO 5A resistive load O Vdc for SSR Not present f Output 4 Out4 R Relay SPST NO 5A resistive load O Vdc for SSR...

Page 20: ...Ascon Tecnologic K31D OPERATING INSTRUCTIONS PAG 20 ...

Reviews: