Ascon Tecnologic - Z31V - OPERATING INSTRUCTIONS - PAG. 5
6. ACCESSORIES
The instrument is equipped with a 5-pole connector that con-
nects the following accessories.
6.1
Parameters configuration by “A01”
The
A01
device connects to the 5-pole connector of the
instrument and allows the transfer of operating parameters
to and from the instrument.
This device it is mainly usable for the serial programming of
some instruments which need to have the same parameters
configuration or to keep a copy of the parameters setting of an
instrument and allow its rapid retransmission.
The same device allows to connect a PC via USB with which,
through the appropriate configuration software for “
AT Univer-
salConf tools
”, the operating parameters can be configured.
To use the
A01
device, the
A01
or the instrument must be cor-
rectly supplied.
AC supply
Supply adapter
12 VDC
Power
supply
Ente
r
PW
S
12
V
A B C
TTL
+
-
US
B
to PC
USB
Ente
r
PW
S
12
V
A B C
TTL
+
-
US
B
to PC
USB
For additional info, please have a look at the
A01
instruction
manual.
7. PROGRAMMABLE PARAMETERS TABLE
Here below is a description of all the parameters available
on the instrument. Some of them may not be present, either
due to the fact they depend on the type of instrument or be-
cause they are automatically disabled as unnecessary.
i. - Measuring inputs parameters
Parameter
Description
Range
Default Note
1
i.se
Probe type
Pt
PTC thermistor
nt
NTC thermistor
nt
2
i.uP
Unit of measurement and
resolution (decimal point)
C0
°C, resolution 1°
F0
°F, resolution 1°
C1
°C, resolution 0.1°
F1
°F, resolution 0.1°
C1
3
i.Ft
Measurement filter
oF
0.1 ÷ 20.0 s
2.0
4
i.C1
Probe Calibration
-30.0 ÷ 30.0°C/°F
0.0
A - Alarm parameters
Parameter
Description
Range
Default Note
5
A.HA
High temperature Alarm
threshold
oF
Disabled;
-99.9 ÷ +999°C/°F.
oF
6
A.LA
Low temperature Alarm
threshold
oF
Disabled;
-99.9 ÷ +999°C/°F
oF
7
A.Ad
Temperature Alarms
Differential
0.0 ÷ 30.0°C/°F
1.0
8
A.At
Temperature Alarms
Delay
oF
Disabled;
0.01 ÷ 9.59 (min.s ) ÷ 99.5 (min.s x 10).
oF
9
A.PA
Temperature Alarms
delay at power ON
oF
Disabled;
0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10).
oF
or. - Buzzer configuration parameter
Par.
Description
Range
Def.
Note
10
o.bu
Buzzer operation
oF
Disabled;
1
Sounds for alarms only;
2
Sounds for key pressure only
3
Sounds for alarms and key pressures.
3
t. - Keyboard configuration parameter
Par.
Description
Range
Def.
Note
11
t.Lo
Keyboard lock function delay
oF
Disabled;
0.01 ÷ 9.59 (min.s) ÷ 30.0 (min.s x 10). oF
12
t.PP
Password to Access
Parameter functions
oF
Disabled;
001 ÷ 999.
oF