6.  ACCESSORIES

The instrument is equipped with a 5-pole connector that con-
nects the following accessories.

6.1 

Parameters configuration by “A01”

The 

A01

 device connects to the 5-pole connector of the 

instrument and allows the transfer of operating parameters 
to and from the instrument.

This device it is mainly usable for the serial programming of 
some instruments which need to have the same parameters 
configuration or to keep a copy of the parameters setting of an 
instrument and allow its rapid retransmission.
The same device allows to connect a PC via USB with which, 
through the appropriate configuration software for “

AT Univer-

salConf tools

”, the operating parameters can be configured.

To use the 

A01

 device, the 

A01

 or the instrument must be cor-

rectly supplied.

AC supply

Supply adapter

12 VDC

Power 
supply

Ente

r

PW
S

12 
V

A B C 

TTL

+

-

US
B

to PC

USB

Ente

r

PW
S

12 
V

A B C 

TTL

+

-

US
B

to PC

USB

For additional info, please have a look at the 

A01

 instruction 

manual.

7.  PROGRAMMABLE PARAMETERS TABLE

Here below is a description of all the parameters available 
on the instrument.  Some of them may not be present, either 
due to the fact they depend on the type of instrument or be-
cause they are automatically disabled as unnecessary.

i. -  Measuring inputs parameters

Parameter

Description

Range

Default Note

i.se

Probe type

Pt

  PTC thermistor

nt

  NTC thermistor

nt

i.uP

Unit of measurement and 

resolution (decimal point)

C0

  °C, resolution 1°

F0

  °F, resolution 1°

C1

  °C, resolution 0.1°

F1

  °F, resolution 0.1°

C1

i.Ft

Measurement filter

oF

0.1 ÷ 20.0 s

2.0

i.C1

Probe Calibration

-30.0 ÷ 30.0°C/°F

0.0

A -  Alarm parameters

Parameter

Description

Range

Default Note

A.HA

High temperature Alarm 

threshold

oF

 Disabled;

-99.9 ÷ +999°C/°F.

oF

A.LA

Low temperature Alarm 

threshold

oF

 Disabled;

-99.9 ÷ +999°C/°F

oF

A.Ad

Temperature Alarms 

Differential

0.0 ÷ 30.0°C/°F

1.0

A.At

Temperature Alarms 

Delay

oF

 Disabled;

0.01 ÷ 9.59 (min.s ) ÷ 99.5 (min.s x 10).

oF

A.PA

Temperature Alarms 

delay at power ON

oF

 Disabled;

0.01 ÷ 9.59 (h.min) ÷ 99.5 (h.min x 10).

oF

or. - Buzzer configuration parameter

Par.

Description

Range

Def.

Note

10 

o.bu

Buzzer operation

oF

 Disabled;

1

 

Sounds for alarms only;

2

 

Sounds for key pressure only

3

 

Sounds for alarms and key pressures.

3

t. -  Keyboard configuration parameter

Par.

Description

Range

Def.

Note

11 

t.Lo

Keyboard lock function delay

oF

 Disabled;

0.01 ÷ 9.59 (min.s) ÷  30.0 (min.s x 10). oF

12 

t.PP

Password to Access 

Parameter functions

oF

 Disabled;

001 ÷ 999.

oF

Summary of Contents for Z31V

Page 1: ...o be equipped with additional electromechanical devices which will guarantee safety 1 INSTRUMENT DESCRIPTION 1 1 General description The Z31V is a digital electronic microprocessor thermometer equipped with functions for temperature alarms The instrument has 1 input for PTC or NTC temperature probes and can be equipped with either an internal buzzer or a relay output for alarm signaling The Z31SV ...

Page 2: ...ord that can be personalised through t PP parameter To protect the parameters set the desired password number at t PP parameter When the protection is active press the key to access the parameters and keep it pressed for about 5 s after which the display shows r P Press the key again the display will show 0 at this point using the and keys set the programmed password number and press the key again...

Page 3: ... Panel cut out 29 0 6 71 0 6 mm RECOMMENDED PANEL CUTOUT min 12 mm min 15 mm 4 2 3 Mounting mm Type 2 gasket max 12 mm Type 1 gasket 29 mm max 34 43 Type 2 Type 1 Butterfly type brackets Screw type bracket 86 4 3 Electrical connections Carry out the electrical wiring by connecting only one wire to each terminal according to the following diagram checking that the power supply is the same as that i...

Page 4: ...ured at that moment The variables display mode is automatically abandoned after about 15 seconds from the last pressure of the key 5 2 Alarm functions The alarm conditions of the instrument are Probe errors E1 and E1 Temperature alarms Hi and Lo The alarm functions act on the LED the internal buzzer if present and configured by the parameter o bu and the relay output if present The parameter o bu ...

Page 5: ...m may not be present either due to the fact they depend on the type of instrument or be cause they are automatically disabled as unnecessary i Measuring inputs parameters Parameter Description Range Default Note 1 i se Probe type Pt PTC thermistor nt NTC thermistor nt 2 i uP Unit of measurement and resolution decimal point C0 C resolution 1 F0 F resolution 1 C1 C resolution 0 1 F1 F resolution 0 1...

Page 6: ...0 AC frequency 50 60 Hz Power consumption About 4 VA Inputs 1 input for temperature probes NTC 103AT 2 10 kW 25 C or PTC KTY 81 121 990 Ω 25 C Output 1 relay output SPDT or SPST NO 16A AC1 6A AC3 250 VAC 1 HP 250 VAC 1 2HP 125 VAC 12 A max for the common pole of removable terminal block model Relay output electrical life SPST NO 100000 operations SPDT 50000 operations VDE omologation Action type T...

Page 7: ...t Relay SPST NA 16A AC1 resistive load S Out Relay SPDT 16A AC1 resistive load d Terminal block Screw terminals standard E Removable screw terminal block complete N Removable screw terminal block the fixed part only e Display Red B Blue c Buzzer Not present B With Buzzer c a b d e f g h f h Reserved codes ii jj Special codes ii jj g Packaging Bracket type AT package Butterfly brackets std V AT pac...

Page 8: ...Ascon Tecnologic Z31V OPERATING INSTRUCTIONS PAG 8 ...

Reviews: