5  FUNCTIONS

5.1 

ON/Stand-by Function

Once powered the instrument can assume 2 different conditions:

ON:

  The controller uses the control functions.

STAND-BY: 

The controller uses no control function and the 

display is turned OFF except for the Stand-by LED.

The transition between Standby and ON status is equivalent 
to power ON the instrument providing the electrical power.
In case of power failure, the system always sets itself in the 
condition it was in before the black-out.
The ON/Stand-by function can be selected: 

 

Pressing the key  /  for at least 1 s if 

t.UF

 = 

3

;

 

Pressing the key   for at least 1 s if 

t.Fa

 = 

3

;

 

Pressing the key   for at least 1 s if 

t.Fb

 = 

3

;

 

Using the Digital Input if parameter 

i.Fi

 = 

3

.

5.2 

Measure and Display configuration

Through parameter 

i.uP

 it is possible to select the tempera-

ture engineering unit and the desired measure resolution 
(C0 = °C/1°; C1 = °C/0.1°; F0 = °F/1°; F1 = °F/0.1°).
The instrument allows the measure calibration, which can be 
used to re-calibrate the instrument according to application 
needs, through the parameters 

i.C1

 (for input 

Pr1

), 

i.C2

 (for 

input 

Pr2

) and 

i.C3

 (for input 

Pr3

).

While 

Pr1

 probe measure is always the 

r1

 controller process 

value, 

i.P2

 and 

i.P3

 parameters allow to select the 

Pr2

 and 

Pr3

 measures usage according to the following possibilities:

r2

 

Controller 2 probe: the probe can be used as process 
value for regulator 

r2

;

Au

 

Auxiliary probe: the probe can be used as a display-
only probe to which temperature alarms can be linked;

dG

 

Digital input (see Digital input functions);

If probe 

Pr2

 and/or 

Pr3

 is/are not used, set the relative pa-

rameters 

i.P2

 and/or 

i.P3

 = 

oF

.

It is not possible to program the two parameters for the same 
function, if so, priority goes to 

i.P2

.

Using 

i.Ft

parameter can be set a software filter for measur-

ing the input values in order to decrease the sensibility to 
fast temperature changes (increasing the sampling time).
Through the 

i.dS

 parameter is possible to set the variable 

normally displayed:

P1

 Probe 

Pr1

 measurement;

P2

 Probe 

Pr2

 measurement;

P3

 Probe 

Pr3

 measurement;

S1

 Controller 

r1

 Set Point;

S2

 Controller 

r2

 Set Point;

1.2

 Probes 

Pr1

 and 

Pr2

 measurements;

1.3

 Probes 

Pr1

Pr2

 and 

Pr3

 measurements;

oF

 

Numerical display switched OFF.

If one of the alternated variable display options (

1.2

 and 

1.3

is selected, using the

 i.td

 parameter it is possible manage 

the display time of the variables.
In these modes the instrument shows for about 1 s the code 
of the variable (

P1

P2

P3

), then the value of its measure-

ment for the time established with 

i.td

, elapsed which it 

switches to the code of the next variable and so on.
Regardless of what has been set set for 

i.dS

 parameter, it is 

possible to ciclically view all the measurement and operat-
ing variables by repeatedly pressing and releasing the   
key.  The display shows the code that identifies the variable 
alternated to its value.

The variables that can be displayed are:

Pr1

 Probe 

Pr1

 measurement;

Pr2

 Probe 

Pr2

 measurement (on/oF if set as digital input);

Pr3

 Probe 

Pr3

 measurement (on/oF if set as digital input).

The system automatically exits the variable display mode 
after 15 s from the last   key pressure.

Note: 

The 

i.uP

 parameter relative to temperature resolution 

acts only for display and Set Points, while in the tem-
perature parameters the decimal is always visible.

5.3 

Digital Input Configuration

As an alternative to one of the measurement inputs 

Pr2

 or 

Pr3

, the user can set the instrument to use it as a digital 

input for voltage-free contacts.
The digital input function (available ON terminal 

11

 as an 

alternative to 

Pr2

 input if 

i.p2

 = 

dg

 or ON terminal 

12

 as 

an alternative to 

Pr3

 input if 

i.p3

 = 

dg

) is defined using the 

i.Fi

 parameter and the action is delayed for the time pro-

grammed with parameter 

i.ti

.  The 

i.Fi

 parameter can be 

configured for the following functions:

No function;

External alarm signal via NO contact: closing the digital 
input (and after the 

i.ti

 time) the alarm is activated and 

the instrument alternately shows ON the display the label 

AL

 and the variable set at parameter 

i.dS

.

External alarm signal with all control outputs disable via 
NO contact: closing the digital input (and after the 

i.ti

 

time), all the control output are disabled, the alarm is 
activated and the instrument alternately shows ON the 
display the label 

AL

 and the variable set at parameter 

i.dS

.

Instrument Switch ON/OFF (ON/Stand-by) of instrument  
via NO contact: closing the digital input (and after the 

i.ti

 

time) the instrument is switched 

ON

 while it is placed in 

Stand-by

 when the digital input is open.

Auxiliary (

Aux

) output remote control via NO contact: clos-

ing the digital input (and after the 

i.ti

 time) the auxiliary 

output is activated as described at auxiliary output 

i.Fo

 = 

3

 

function mode.

Cell door opening with fan stop via NO contact: closing 
the digital input (and after the 

i.ti

 time) the fans are 

stopped and the instrument alternately shows ON the dis-
play the label 

op

 and the variable set at parameter 

i.dS

.  

With this function mode, the action of the digital input also 
activates the time that can be set with parameter 

A.oA

 af-

ter which the alarm is activated to point out that the door 
has been left open and the fan restarts.

Cell door opening without fan stop via NO contact: closing 
the digital input (and after the 

i.ti

 time) the instrument 

alternately shows ON the display the label 

op

 and the 

variable set at parameter 

i.dS

.  With this function mode, 

the action of the digital input also activates the time that 
can be set with parameter 

A.oA

 after which the alarm is 

activated to point out that the door has been left open.

-1

-2

-3

-4

-5

-6

 

These functions are like those just described, but work 
with a reversed logic as the contact is NC.

When an input is configured as digital, it is possible to check 
its status using the variable display mode through the   key 
or by configuring the normal display via 

i.dS

 for the input 

configured as digital.  The display shows 

oF

 if the digital 

input is open and 

on

 if closed.

Summary of Contents for Y39W

Page 1: ...studied in particular to manage refrigeration units display cases etc typically in tended for the storage and distribution of wines and or drinks in domestic or commercial uses The instrument is equi...

Page 2: ...both loops programmed for heating action but with parameter t Ld 2 this LED shows the r1 controller status while the status of controller r2 is shown by Aux LED 8 LED Indicates Defrost in progress ON...

Page 3: ...to 0 now using the keys insert the programmed password number and press the key again If the password is correct the instrument displays the code of the first parameter and it will be possible to pro...

Page 4: ...use of the instrument for applications not expressly permitted by the above mentioned rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous flamma ble or...

Page 5: ...vices ex fuses proportionate to the circulat ing currents It is strongly recommended that cables with proper insula tion according to the working voltages and temperatures are to be used Furthermore t...

Page 6: ...ables that can be displayed are Pr1 Probe Pr1 measurement Pr2 Probe Pr2 measurement on oF if set as digital input Pr3 Probe Pr3 measurement on oF if set as digital input The system automatically exits...

Page 7: ...the following functions oF Buzzer always disabled 1 The Buzzer sounds when an alarm is active 2 The Buzzer sounds when a key pressed does not signal alarms 3 The Buzzer sounds when a key pressed and...

Page 8: ...nfigured for r1 and r2 operation the LEDs still indicate the controllers status If both controllers are configured for the same action r Fc CC HH the or LEDs indicate the activation of at least one of...

Page 9: ...frost the control outputs ot and the Fanscon tinue operating while df output is enabled 5 8 1 Automatic Defrosts Start The automatic control of defrost occours by Interval times For continuous compres...

Page 10: ...s of parameters A y2 and A y2 are 1 Absolute Alarms referred to Pr1 probe 2 Alarms Relative to SP1 referred to pr1 probe 3 Absolute Alarms referred to r2 probe 4 Alarms Relative to SP2 referred to r2...

Page 11: ...e key for at least 5 s it is possible to enable disable a defrost cycle 3 Pressing the key for at least 1 s it is possible to switch the instrument from the ON status to Stand by status and vice versa...

Page 12: ...itch on off Stand by 4 Auxiliary output command 5 Door open with fan stop 6 Door open without fan stop 0 16 i ti Delay in acquiring digital input oF 0 01 9 59 min s 99 5 min s x10 oF 17 i dS Variable...

Page 13: ...H2 e A L2 oF 0 01 9 59 min s 99 5 min s x 10 oF 46 A PA Temperature Alarms delay at power ON oF 01 9 59 h min 99 5 h min x 10 2 00 47 A dA Temperature Alarms delay after defrost oF 0 01 9 59 h min 99...

Page 14: ...with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Electrical Data Power supply 12 VA...

Page 15: ...rective 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER Model Y39W Instrument with mechanical keyboard Y39SW Instrument with...

Page 16: ...Ascon Tecnologic Y39W Line Operating Instructions Pag 16...

Reviews: