Ascon tecnologic Y39W Operating Instructions Manual Download Page 4

Ascon Tecnologic - Y39W Line - Operating Instructions - Pag. 4

2.5 

Reset Parameters to Default Value

The instrument allows the reset of the parameters to those 
values programmed in factory as default.
To restore the default parameters value, set the value 

-48

 at 

r.p

 password request.

Therefore, to make the reset to the default parameters, en-
able the Password using the 

t.PP

 parameter so that the 

r.p

 

setting is requested, at this point insert 

-48

 instead of the 

programmed access password.
Once confirmed the password with the   key, the display 
shows “

---

” for 2 s after which the instrument resets all the 

parameters to the factory default setting.

2.6 

Keyboard Lock Function

On the instrument it is possible to completely lock the key-
board.  This function is useful when the controller is installed 
in an accessible area and changes must be avoided.
To activate the keyboard lock it is enough program the pa-
rameter 

t.Lo

 to a value different than 

oF

.

The 

t.Lo

 value is the keys inactivity time after which the in-

strument  automatically locks the keyboard.  Therefore, press-
ing no buttons for the time set at 

t.Lo

, the normal functions of 

the keys are automatically disabled.
When the keyboard is locked, if any of the key is pressed, 
the display shows 

Ln

 to indicate that the lock is active.

To unlock the keyboard it is enough to contemporarily press 

 +   keys and keep them pressed for 5 s, after which the 

label 

LF

 appears on the display and all the key functions will 

be available again.

3  USAGE WARNINGS 

3.1 

Admitted Usage

The instrument has been projected and manufactured 
as a measuring and control device to be used accord-
ing to EN60730-1 at altitudes operation below 2000 m.

 The use of the instrument for applications not expressly 
permitted by the above mentioned rule must adopt all the 
necessary protective measures.
The instrument 

MUST NOT BE USED

 in dangerous (flamma-

ble or explosive) environments without adequate protections.
The instrument used with NTC 103AT11 probe (identifiable by 
the printed code “103AT-11” visible on the sensor part) is com-
pliant with standard EN 13485 (“Thermometers for measuring 
the air and product temperature for the transport,storage and 
distribution of chilled, frozen, deep-frozen/quick-frozen food 
and ice cream”) with the following classification: 
[EN13485 air, S, A, 2,- 50°C +90°C]
Remember that the end user must periodically check and veri-
fy the thermometers in compliance with standard EN 13486.
The installer must ensure that EMC rules are respected, also 
after instrument installation, if necessary using proper filters.

4  INSTALLATION WARNINGS

4.1 

Mechanical Mounting

The instrument, in case 78 x 35 mm, is designed for flush-
in panel mounting.  Make a hole 71 x 29 mm and insert the 
instrument, fixing it with the provided special brackets.
In order to obtain the declared front protection degree, use 
the screw type bracket (optional).
Avoid placing the instrument in environments with very high 
humidity levels or dirt that may create condensation or intro-
duction of conductive substances into the instrument.
Ensure adequate ventilation to the instrument and avoid 
installation in containers that house devices which may 
overheat or which may cause the instrument to function at a 
higher temperature than the one permitted and declared.
Connect the instrument as far away as possible from sourc-
es of electromagnetic disturbances such as motors, power 
relays, relays, solenoid valves, etc..

4.2 

Dimensions 

[mm]

4.2.1  Mechanical Dimensions

Y39W

35

78

28

12.2

14.5

8

6

64

4.2.2  Panel Cut-Out

86 min.

41 min.

71

+0.6

29

+0.6

Summary of Contents for Y39W

Page 1: ...studied in particular to manage refrigeration units display cases etc typically in tended for the storage and distribution of wines and or drinks in domestic or commercial uses The instrument is equi...

Page 2: ...both loops programmed for heating action but with parameter t Ld 2 this LED shows the r1 controller status while the status of controller r2 is shown by Aux LED 8 LED Indicates Defrost in progress ON...

Page 3: ...to 0 now using the keys insert the programmed password number and press the key again If the password is correct the instrument displays the code of the first parameter and it will be possible to pro...

Page 4: ...use of the instrument for applications not expressly permitted by the above mentioned rule must adopt all the necessary protective measures The instrument MUST NOT BE USED in dangerous flamma ble or...

Page 5: ...vices ex fuses proportionate to the circulat ing currents It is strongly recommended that cables with proper insula tion according to the working voltages and temperatures are to be used Furthermore t...

Page 6: ...ables that can be displayed are Pr1 Probe Pr1 measurement Pr2 Probe Pr2 measurement on oF if set as digital input Pr3 Probe Pr3 measurement on oF if set as digital input The system automatically exits...

Page 7: ...the following functions oF Buzzer always disabled 1 The Buzzer sounds when an alarm is active 2 The Buzzer sounds when a key pressed does not signal alarms 3 The Buzzer sounds when a key pressed and...

Page 8: ...nfigured for r1 and r2 operation the LEDs still indicate the controllers status If both controllers are configured for the same action r Fc CC HH the or LEDs indicate the activation of at least one of...

Page 9: ...frost the control outputs ot and the Fanscon tinue operating while df output is enabled 5 8 1 Automatic Defrosts Start The automatic control of defrost occours by Interval times For continuous compres...

Page 10: ...s of parameters A y2 and A y2 are 1 Absolute Alarms referred to Pr1 probe 2 Alarms Relative to SP1 referred to pr1 probe 3 Absolute Alarms referred to r2 probe 4 Alarms Relative to SP2 referred to r2...

Page 11: ...e key for at least 5 s it is possible to enable disable a defrost cycle 3 Pressing the key for at least 1 s it is possible to switch the instrument from the ON status to Stand by status and vice versa...

Page 12: ...itch on off Stand by 4 Auxiliary output command 5 Door open with fan stop 6 Door open without fan stop 0 16 i ti Delay in acquiring digital input oF 0 01 9 59 min s 99 5 min s x10 oF 17 i dS Variable...

Page 13: ...H2 e A L2 oF 0 01 9 59 min s 99 5 min s x 10 oF 46 A PA Temperature Alarms delay at power ON oF 01 9 59 h min 99 5 h min x 10 2 00 47 A dA Temperature Alarms delay after defrost oF 0 01 9 59 h min 99...

Page 14: ...with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alterna tive agreements 10 TECHNICAL DATA 10 1 Electrical Data Power supply 12 VA...

Page 15: ...rective 2006 95 CE EN 60730 1 EN 60730 2 9 Regulation 37 2005 CE EN13485 air S A 2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER Model Y39W Instrument with mechanical keyboard Y39SW Instrument with...

Page 16: ...Ascon Tecnologic Y39W Line Operating Instructions Pag 16...

Reviews: