Model KR1E
22/03 - Code: ISTR_Q_KR1E_E_06_--
DECLARATION OF CONFORMITY AND
MANUAL RETRIEVAL
KR1E is a panel mounting, Class II instrument designed to comply
with European directives. All information about the controller use
can be found in the “Engineering Manual”.
The Declaration of Conformity and the manual of the controller
can be downloaded (free of charge) from the web-site:
www.ascontecnologic.com
Once connected to the web-site, search:
KR1E
then click on
KR1E
.
In the lower part of the product page (in any language) is present
the download area with links to the documents available for the
controller (in the available languages).
Warning
!
- Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, things or animals, please
remember that the plant must be equipped with additional
devices which will guarantee safety.
- We warrant that the products will be free from defects in material and
workmanship for 18 months from the date of delivery. Products
and components that are subject to wear due to conditions of
use, service life and misuse are not covered by this warranty.
Disposal
The appliance (or the product) must be disposed
of separately in compliance with the local
standards in force on waste disposal.
KR1E
PV
AT
Access to:
- Operator Commands
- Parameters
- Configuration
Access to:
- Operator additional information
- Set Point
Increase the displayed
value/Selects the para-
meters list next element
Decrease the displayed
value or select the
previous element
Exit from Operator
commands/Parameter
setting/Configuration
Programmable key:
Start the programmed function
(Autotune, Auto/Man, Timer ...)
Access to:
- Set Point
Operator Mode
Editing Mode
Confirm and go to
Next parameter
These 2 keys, pressed in sequence, allow to toggle
between MANual and AUTO modes.
+
Process Value
(in eng. units)
Output LEDs
Manual mode
Alarm active
Unit (°C/°F)
Autotune in progress
(flashing)
DISPLAY AND KEYS
Set Point
(auto mode)
Output Value
(manual mode)
Parameter value
or
State/
Function selected
(editing mode)
MODEL CODE
The Hardware resources are identified by the following Model Code.
KR1E
A B C D E F G H
Model:
Supply voltage: 100... 240 Vac/
18... 28 Vac/
20... 30 Vdc
ELECTRICAL CONNECTIONS
RS485
DI1
OP3
OP2
NO
NO
C
C
C
NO
NF
Pt100
Pt1000/NTC/PTC
OP4
(note)
DI2
(note)
Ananogue Input
12 Vdc
(note)
12 Vdc
(note)
PV
PV
4... 20 A
3 wire transmitter
2 wire
transmitter
OP1
TERMINALS
Note:
Terminal 4 can be programmed as:
- Digital Input
(DI2) connecting a free of voltage contact between terminals 4 and 11;
- 0... 12 V SSR Drive Output
(OP4) connecting the load between terminals 4 and 11;
- 12 Vdc transmitter power supply
connecting the 2 wire transmitter between terminals 4 and 1;
for 3 wire transmitter connect terminal 4 to transmitter power supply input and terminal 1 and 2 to transmitter signal output.
: Out4 has a Logic Level 1 of: 12 VDC ±20%, 20 mA max.
mA
L
Pin:
q
2.5 mm (0.1 in.) max.
Stripped wire: L 5.5 mm (0.21 in.)
Neutral Line
Power supply
MOUNTING
DIMENSIONS
Overall dimensions (L x H x D): 78 x 35 x 69.5 mm
(3.07 x 1.37 x 2.73 in.)
Panel Cut-out (L x H):
71+0.6 x 29+0.6 mm
(2.79+0.023 x 1.14+0.023 in.)
Attention
The controller can be installed using 2 different types of brackets.
Follow the sequence 1, 2a, 3a for the screw bracket (collar
bracket for IP65), the sequence 1, 2b, 3b for the “butterfly”
brackets (2 pieces).
2a
2a
3b
3b
1
3a
3a
1
2b
2b
KR1E
KR1E
KR1E
Press for 2 seconds
the key
PARAMETERS SETTING
CONTROLLER DISPLAY
Increases the displayed value
Confirm value and pass to the next parameter
Decreases the displayed value
Parameter setting
To exit the parameters configuration procedure, press
for 3 seconds or wait for the end of the delay
(about 10 seconds)
The
KR1E-xDRRRDxx
controller is pre-configured (default
configuration) for wine applications where there is the
need to cool or reheat in thermostatic mode (on/off with
hysteresis) a tank with a PT100 probe in mono relay
output (Heat and Cool on OP1).
Heat mode
The controller action type can be identified by the color of the upper display (measurement):
Red
:
Heat mode only
Green
: Cool mode only
Orange
: The controller responds to temperature changes and selects the appropriate control mode
by operating the appropriate control output and displaying the setpoint to be reached.
The numbered red LEDs indicate, when lighted, the active (on) state of the corresponding relay output.
Cool mode
Automatic Heat/Cool
selection
2 s
KR1E
KR1E
KR1E
KR1E
Line
KR1E
Power Supply
A
24Vac (-25... +12%) or 24Vdc (-15... +25%)
L
100... 240 Vac (-15... +10%)
H
Input + Ditigal input1
B
PT100, PT1000, mA + Digital Input 1
D
PTC, NTC, mA + Digital Input 1
P
Output OP1 (control output)
C
Relay (1 SPST NO, 4 A/250 Vac)
R
Output OP2 (control output)
D
Relay SPST NO 2 A/250 Vac (resistive load)
R
Output OP3 (alarm output)
E
None
-
Relay SPST NO 2 A/250 Vac (resistive load) selectable if Output 1 is present
R
Output OP4 (configurable)
F
Digital I/O (see the Electrical Connections paragraph for details)
D
Serial Communications
G
TTL Modbus
-
RS485 Modbus
S
Terminal Type
H
Standard (screw type non removable terminal blocks)
-
With plug-in screw type terminal blocks
E
With plug-in clamp type terminal blocks
M
With plug-in terminal blocks (fixed part only)
N
Model Code example:
KR1E-LDRRRD-E
KR1E controller for Wine applications
-
Power supply: 24Vac/dc,
-
Inputs: PT1000 or 4... 20 mA;
-
Digital Input 1,
-
3 Relay Outputs (OP1: Alarm, OP2: Cold, OP3 Alarm),
-
Confiigurable OP4: Digital Input 2 or Transmitter power supply,
-
TTL Port,
-
Removable screw type terminals.
Parameters List (
PASS
: 30)
Group Param.
Description
Value range or selection list
Default
User
selection
Note
inp
node
Control mode selection
1 Heat (SP on Out1)
or
Cool (SP2 on Out1),
2
Heat (SP on Out1)
or
Cool (SP2 on Out2),
3 Heat (SP on Out1)
and
Cool (SP2 on Out2),
4 Heat
(SP on Out1)
or
Cool(SP2 on Out2)
or
Heat
(SP on Out1)
and
Cool (SP2 on Out2),
5 Heat
(SP on Out1)
or
Cool (SP on Out1),
6 Heat
(SP on Out1)
or
Cool (SP on Out2),
7 Heat
(SP on Out1)
and
Cool (SP on Out2),
8 Heat (SP on Out1)
or
Cool (SP on Out2)
or
Heat
(SP on Out1)
and
Cool (SP on Out2).
1
sEns
Measurement input type
Pt1
Pt100
Pt10 Pt1000
4.20 4… 20 mA
Pt1
dp
Decimal point position
0... 3
0
diF1
Digital input 1 function
Stby Mode Standby (transition)
Stb2 Mode Standby (status)
HC.tr Heat <-> Cool (transition)
HC.St Heat <-> Cool (status)
nonE
diF2
Digital input 2 function
nonE
di.a
Digital Inputs Action
0... 3
0
See the manual for details
Pan
usrb
Key
function
Stby Standby Mode
1H2C Heat <-> Cool toggle
HC.Sb Heat <-> Cool and
Auto <-> Standby
Auto
If
HC.Sb
: a 1 s pressure
toggles between
Heat <-> Cool mode.
A 5 s pressure puts the
controller in standby
ser
Add
Controller Modbus address
1... 254
1
Modbus RTU slave
Protocol
bAud
Modbus transmission speed
1200, 2400, 9600 baud,
19.2, 38.4 kbaud
9600
Notes: 1.
Several successive pressures on the key allow the various groups of parameters to be scrolled.
2.
A long pressure on the key allows to exit the Configuration mode and return to the operator mode
Parameters List (
PASS
: 20)
Param.
Description
Value range or selection list
Default
User
selection
Note
OpEr
Operative mode selection
reg
Auto,
stby Standby
reg
st.by
: Control action stopped
reg
: Control action running
SP
Set point 1
-1999... +9999 (Engineering Unit) 0
SP2
Set point 2
-1999... +9999 (Engineering Unit) 0
HstH
Heat Hysteresis
0... 9999 (Engineering Unit)
1
HstC
Cool Hysteresis
0... 9999 (Engineering Unit)
1
AL1
Alarm 1 threshold (Low)
AL1L... AL1H
0
AL2
Alarm 2 threshold (High)
AL2L... AL2H
80
dP
Decimal point position
0... 3
0
SPLL
Setpoint Low Limit
From 0 to the SPHL value
0
SPHL
Setpoint High Limit
From the value of SPLL to 1999
90
FiL
Digital filter on the measured value 0
oFF
0.1... 20.0 s
1.0
HAL1
Alarm 1 Hysteresis
0...9999 (Engineering Unit)
1
HAL2
Alarm 2 Hysteresis
0...9999 (Engineering Unit)
1
Al.o
Adjust Low Offset
-300…+300 (Engineering Unit)
0
Note:
Several successive pressures on the
key allow to scroll the available Control parameters.
m
Pressing no keys for 5 s
, the controller automatically exits
PASS20
menu and returns to the standard display and the current measurement.