WINE CONTROLLER
1/16 DIN - 48 x 48
Model KM1E
Q u i c k G u i d e
•
I S T R - F K M 1 E - E N G 0
1
viale Indipendenza 56, 27029 - Vigevano (PV) - ITALY
Tel.: +39 0381 698 71, Fax: +39 0381 698 730
internet site:
www.ascontecnologic.com
E-mail:
ube
DECLARATION OF CONFORMITY AND
MANUAL RETRIEVAL
KM1E is a panel mounting, Class II instrument. It has been
designed with compliance to the European Directives.
All information about the controller use can be found in the
Engineering Manual:
ISTR-MKM_-ENG0x
(“
x
” is the revision).
The Declaration of Conformity and the manual of the controller
can be downloaded (free of charge) from the web-site:
www.ascontecnologic.com
Once connected to the web-site, search:
KM1E
then click on
KM1E
.
In the lower part of the product page (in any language) is present
the download area with links to the documents available for the
controller (in the available languages).
Warning
!
- Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, things or animals, please
remember that the plant must be equipped with additional
devices which will guarantee safety.
- We warrant that the products will be free from defects in material and
workmanship for 18 months from the date of delivery. Products
and components that are subject to wear due to conditions of
use, service life and misuse are not covered by this warranty.
Disposal
The appliance (or the product) must be disposed of
separately in compliance with the local standards in
force on waste disposal.
KM1E
Process Value
(in eng. units)
Set Point
(auto mode)
Output Value
(manual mode)
Param. value
or
State/Function
(Editing mode)
Output
LEDs
Manual
mode
Alarm
active
Unit
(°C/°F)
Autotune
in progress
(flashing)
DISPLAY AND KEYS
Access to:
- Setpoint adjustment
(SP display)
- Setpoint validation
Increase the displayed
value
Decrease the displayed
value
Back to Operator mode
(long pressure)
Displays the previous parameter
in Control mode (short pressure)
Access to:
Control mode toggle
(Heat/Cool) (pressed for
more than 1 s)
Access to:
- Setpoint adjustment
Access to:
- Setpoint adjustment
Operator Mode
Control Mode
Confirm and go to
Next parameter
MODEL CODE
The Hardware resources are identified by the following Model Code.
KM1E A B C D E F G H
Model:
RS485
DI1
OP3
OP2
OP1
OP4
(note)
DI2 (note)
Analogue input
mA
Note:
Terminal 4 can be programmed as:
- Digital Input
(DI2) connecting a free of
voltage contact between terminals 4 and 16;
- 0... 12 V SSR Drive Output
(OP4) connecting
the load between terminals 4 and 16;
- 12 Vdc (20 mA) transmitter power supply
connecting the 2 wire transmitter between
terminals 4 and 1; for 3 wire transmitter connect
terminal 4 to transmitter power supply input and
terminal 1 and 2 to transmitter signal output.
Neutral
Line
12 VDC
(note)
PV
4... 20 mA
3 wire transmitter
12 VDC
(note)
PV
Pt100
Pt1000/NTC/PTC
4... 20 mA
2 wire transmitter
100... 240 Vac/
18... 28 Vac/
20... 30 Vdc
Power
supply
TERMINALS
Pin connector
q
1.4 mm max.
(0.055 in.)
Stripped wire
L:
5.5 mm
(0.21 in.)
L
ELECTRICAL CONNECTIONS
MOUNTING
2
2
1
1
3
DIMENSIONS
Overall dimensions (L x H x D
max.
): 48 x 48 x 73... 99 mm
(1.89 x 1.89 x 2.78... 3.89 in.)
Panel Cut-out (L x H):
45+0.6 x 45+0.6 mm
(1.78+0.023 x 1.78+0.023 in.)
KM1E
KM1E
KM1E
KM1E
KM1E
KM1E
KM1E
2 s
Press for 2 seconds
on the key
PARAMETERS SETTING
CONTROLLER DISPLAY
Increases the displayed value
Confirm value and pass to the next parameter
Decreases the displayed value
Parameter setting
To exit the parameters configuration procedure, press
for 3 seconds or wait for the end of the delay
(about 10 seconds)
The
KM1E-xDRRRDxx
controller is pre-configured (default
configuration) for wine applications where there is the
need to cool or reheat in thermostatic mode (on/off with
hysteresis) a tank with a PT100 probe in mono relay
output (Heat and Cool on OP1).
Heat mode
The controller action type can be identified by the color of the upper display (measurement):
Red
:
Heat mode only
Green
: Cool mode only
Orange
: The controller responds to temperature changes and selects the appropriate control mode
by operating the appropriate control output and displaying the setpoint to be reached.
The numbered red LEDs indicate, when lighted, the active (on) state of the corresponding relay output.
Cool mode
Automatic Heat/Cool
selection
Line
KME
Power Supply
B
24Vac (-25... +12%) or 24Vdc (-15... +25%)
L
100... 240 Vac (-15... +10%)
H
Input + Ditigal input1
C
PT100, PT1000, mA + Digital Input 1
D
PTC, NTC, mA + Digital Input 1
P
Output OP1 (control output)
D
Relay (1 SPST NO, 4 A/250 Vac)
R
Output OP2 (control output)
E
None
-
Relay SPST NO 2 A/250 Vac (resistive load)
R
Output OP3 (alarm output)
F
None
-
Relay SPST NO 2 A/250 Vac (resistive load) selectable if Output 1 is present
R
Output OP4 (configurable)
G
Digital I/O (see the Electrical Connections paragraph for details)
D
Serial Communications
H
TTL Modbus
-
RS485 Modbus
S
Terminal Type
I
Standard (screw type non removable terminal blocks)
-
With plug-in screw type terminal blocks
E
With plug-in clamp type terminal blocks
M
With plug-in terminal blocks (fixed part only)
N
Model Code example:
KM1E-LDRRRD-E
KM1E controller for Wine applications
- Power supply: 24Vac/dc,
- Inputs: PT1000 or 4... 20 mA +1 Digital Input,
- 3 Relay Outputs (OP1: Alarm, OP2: Cold, OP3 Alarme),
- Confiigurable OP4: Digital Input 2 or Transmitter power supply,
- TTL Port,
- Removable screw type terminals.
Parameters List (
PASS
: 30)
Group Param.
Description
Value range or selection list
Default
User
selection
Note
inp
node
Control mode selection
1
Heat or Cool on OP1 only,
2
Heat (OP1) or Cool (OP2),
3
Heat (OP1) and Cool (OP2),
1
When only 1 output is
present, the controller
does not display the
node
parameter.
It is fixed on “M
ode 1”
sEns
Measurement input type
Pt1 Pt100
Pt10 Pt1000
4.20 4… 20 mA
Pt1
dp
Decimal point position
0... 2
0
diF1
Digital input 1 function
Stby Mode Standby (transition)
Stby2 Mode Standby (status)
HC.tr Chaud <-> Froid (transition)
HC.St Chaud <-> Froid (status)
nonE
diF2
Digital input 2 function
nonE
di.a
Digital Inputs Action
0... 3
0
See the manual for
details
Pan
usrb
Key function
Stby Standby Mode
1H2C Heat <-> Cool toggle
HC.Sb Heat <-> Cool and
Auto <-> Standby
Auto
If
HC.Sb
: a 1 s pressure
toggles between
Heat <-> Cool mode.
A 5 s pressure puts the
controller in standby
ser
Add
Modbus address of the controller 1... 254
1
Modbus RTU slave
Protocol
bAud
Modbus transmission speed
1200, 2400, 9600 baud,
19.2, 38.4 kbaud
9600
Several successive pressures on the key allow the various groups of parameters to be scrolled.
A long pressure on the key allows to exit the Configuration mode and return to the Operator mode
Parameters List (
PASS
: 20)
Param.
Description
Value range or selection list
Default
User
selection
Note
OPEr
Operative mode selection
reg Auto,
stdy Standby
reg
stdy: Control action stopped
reg: Control action running
SP
Set point 1
-1999... +9999 (Engineering Unit) 0
SP2
Set point 2
-1999... +9999 (Engineering Unit) 0
HstH
Heat Hysteresis
0... 9999 (Engineering Unit)
1
HstC
Cool Hysteresis
0... 9999 (Engineering Unit)
1
AL1
Alarm 1 threshold (Low)
AL1L... AL1H
0
AL2
Alarm 2 threshold (High)
AL2L... AL2H
80
dP
Decimal point position
0... 2
0
SPLL
Setpoint Low Limit
From 0 to the SPHL value
0
SPHL
Setpoint High Limit
From the value of SPLL to 1999
90
FiL
Digital filter on the measured value 0 oFF
0.1... 20.0 s
1.0
HAL1
Alarm 1 Hysteresis
0...9999 (Engineering Unit)
1
HAL2
Alarm 2 Hysteresis
0...9999 (Engineering Unit)
1
Al.o
Adjust Low Offset
-300…+300 (Engineering Unit)
0
Note:
Several successive pressures on the key allow to scroll the available Control parameters.
m
Pressing no keys for 5 s
, the controller automatically exits
PASS20
menu and returns to the standard display and the current measurement.