Installation & Maintenance Instructions

SERIES

Form No.V6954

2-WAY AIR OPERATED VALVES

F210

 NORMALLY OPEN OR NORMALLY CLOSED OPERATION

GENERAL SERVICE  -  3/8

I

, 1/2

I

 OR 3/4

I

 NPT

DESCRIPTION

Series  F210  valves  are  2-way  normally  open  or normally

closed air operated valves.  Valves may be provided with an

instrument air operator for a 3-30 psi signal range or with

a fluidic/logic interface air operator for a 1.5-5 psi signal

range.  Series F210 valves are of rugged brass, stainless or

steel construction.

OPERATION

Normally  Open:   

Valve  is  open  when  operator  is

de-pressurized; closed when pressurized.

Normally  Closed:   

Valve  is  closed  when  operator  is

de-pressurized; open when pressurized.
Note:  No  minimum  operating  pressure  differential

required.

Manual Operator  

Normally Open Construction Only

(optional feature

)

Manual operator allows manual operation when desired or

during  a  loss  of  auxiliary  pressure.    To  engage  manual

operator (close the valve), press stem inward or rotate stem

locknut clockwise until it stops.  Valve will be in the same

position as when the operator is pressurized.  To disengage

manual  operator  (open  the  valve),  release  stem  or  rotate

stem locknut counterclockwise until it stops.

  CAUTION:  For valve to be operated by auxiliary

pressure, manual operator stem locknut must be fully

rotated counterclockwise.

Turn stem locknut

clockwise to close

valve.  Turn stem locknut

counterclockwise

to open valve and

return to auxiliary

pressure operation

of the valve.

ÎÎÎÎ

ÎÎÎÎ

Push stem inward to

close valve.  Release of

stem  returns  valve  to

open position.

Manual operator

INSTALLATION

Check  nameplate  for  correct  catalog  number,  pressure

(main and auxiliary) and service.  Never apply incompatible

fluids or exceed pressure rating of the valve.  Installation and

valve maintenance to be performed by qualified personnel.

Air Operator Specifications

S

Instrument air operator signal pressure range is 3-30

psi.

S

Fluidic/Logic  interface  air  operator  signal  pressure

range is 1.5-5 psi.

Future Service Considerations

Provision  should  be  made  for  performing  seat  leakage,

external leakage, and operational tests on the valve with a

nonhazardous, noncombustible fluid after disassembly and

reassembly.

Temperature Limitations

S

Normal ambient temperature range is 32

_

F (0

_

 C) to

125

_

F (52

_

 C).

S

Maximum  fluid  temperature  180

_

F  (82

_

C)  for

instrument air operator (3-30 psi range).

S

Maximum  fluid  temperature  150

_

F  (65

_

C)  for  low

pressure air operator (1.5 - 5 psi range).

Positioning

This valve is designed to perform properly when mounted in

any position.  However, for optimum life and performance,

the  operator should be mounted vertically and upright to

reduce the possibility of foreign matter accumulating in the

air operator area.

Mounting

For mounting bracket (optional feature) dimensions, refer

to Figure 1.

Figure 1.  Mounting bracket dimensions

[42]

1.66

.28 dia.

2 mounting holes

[    7.1]

Ø

Piping

Connect piping or tubing to valve according to markings on

valve body.  Apply pipe compound sparingly to male pipe

threads only.  If applied to valve threads, the compound may

enter the valve and cause operational difficulty.  Avoid pipe

strain  by  properly  supporting  and  aligning  piping.    When

tightening the pipe, do not use valve or operator as a lever.

Locate wrenches applied to valve body or piping as close as

possible to connection point.