background image

Page 1 of 3

50 Hanover Road, Florham Park, New Jersey 07932    www.ascovalve.com

All Rights Reserved.

E176557

Installation & Maintenance Instructions

SERIES

I&M No.V7517

2-WAY DIRECT LIFT SOLENOID VALVES

8030

NORMALLY CLOSED OPERATION

BRASS OR STAINLESS STEEL CONSTRUCTION

 3/4

I

 NPT   LOW PRESSURE SERVICE

NOTICE:    See  separate  solenoid  installation  and

maintenance  instructions  for  information  on:  Wiring,

Solenoid Temperature, Cause of Improper Operation, Coil

or Solenoid Replacement.

DESCRIPTION

Series  8030  valves  are  2-way  normally  closed  direct  lift

solenoid  valves  designed  for  low  pressure  service.    Valves  are

made  of    rugged  forged  brass  or  stainless  steel.    Series  8030

valves  may  be  provided  with  a  general  purpose/watertight,

open-frame or watertight/explosionproof solenoid.

OPERATION

Normally  Closed:

    Valve  is  closed  when  solenoid  is

de-energized; open when energized.

NOTE:    No  minimum  operating  pressure  differential

required.

Manual Operator (optional feature)

Manual operator allows manual operation when desired or

during  an  electrical  power  outage.  To  engage  manual

operator (open the valve), turn stem clockwise until it hits

a stop. Valve will now be in the same position as when the

solenoid is energized. To disengage manual operator (close

the valve), turn stem counterclockwise until it hits a stop.

CAUTION:  For valve to operate electrically, manual

operator stem must be fully rotated counterclockwise.

INSTALLATION

Check  nameplate  for  correct  catalog  number,  pressure,

voltage,  frequency, and service. Never apply incompatible

fluids or exceed pressure rating of the valve. Installation and

valve maintenance to be performed by qualified personnel.

Future Service Considerations

Provision  should  be  made  for  performing  seat  leakage,

external leakage, and operational tests on the valve with a

nonhazardous, noncombustible fluid after disassembly and

reassembly.

Temperature  Limitations

Valves  with  design  change  letter  K"  or  P"  within  the

catalog number (example: 8030K043) have a maximum fluid

temperature  of  180

_

F.  Refer  to  separate  solenoid

Installation  and  Maintenance  Instructions  for  maximum

ambient temperature.

Positioning

Valve is designed to perform properly when mounted in any

position.  However, for optimum life and performance, the

solenoid should be mounted vertical and upright to reduce

the  possibility  of  foreign  matter  accumulating  in  the

solenoid base sub-assembly area.

Mounting

Refer to Figure 1 for mounting bracket (optional feature)

mounting dimensions.

Figure 1. Mounting Bracket Dimensions.

[42]

1.66

.28 dia.

2 mounting holes

[    7.1]

Ø

Piping

Connect  piping  to  valve  according  to  markings  on  valve

body.  Apply pipe compound sparingly to male pipe threads

only. If applied to valve threads, the compound may enter

the valve and cause operational difficulty. Avoid pipe strain

by  properly  supporting  and  aligning  piping.  When

tightening the pipe, do not use valve or solenoid as a lever.

Locate wrenches applied to valve body or piping as close as

possible to connection point.

  CAUTION:  To protect the solenoid valve, install a

strainer or filter suitable for the service involved in the

inlet  side  as  close  to  the  valve  as  possible.  Clean

periodically  depending  on  service  conditions.  See

ASCO Series 8600, 8601 and 8602 for strainers.

Reviews: