6. Insert the ground screw (M5) into the functional ground screw opening on the front panel.
7. Use a ratcheting torque screwdriver to tighten the ground screws and ring terminal to the switch
front panel. The torque should not exceed 6 kg-cm (5.2 lb-in).
8. Attach the other end of the ground wire to an appropriate ground, such as a ground bus, a grounded
DIN rail, or a grounded bare rack.
Prepare the installation site
Cabling Infrastructure
: Ensure the cabling infrastructure meets the necessary network specifications.
Installation Location
: Before installing the switch, plan its location and orientation relative to other
devices and equipment:
n
In the front of the switch, leave a minimum of 6 inches (15.24 cm) of space for the twisted-pair and fiber-
optic cabling.
n
In the back of the switch, leave a minimum of 6 inches (15.24 cm) of space for the power cord.
Cooling air flow in Aruba 10000 switches is Port-to-Power or Power-to-Port, depending on which power
supply and fan tray options are installed. To reverse the cooling air flow direction in an 10000 switch, you
must replace the existing power supplies and fan trays with power supplies and fan trays having the
opposite air flow direction. All fan trays and power supplies installed in an 10000 switch must have the same
air flow direction. See
for further detail.
To avoid personal injury or product damage, review
Installation precautions and guidelines
before starting
installation.
Install power supplies
Skip this step if two power supplies are already installed in the switch
If two power supplies are not already installed in the switch, install matching power supplies in both slots
before proceeding.
n
Aruba CX 10000-48Y6C Port to Power (FB) AC Power Supply Unit (R8R51A)
n
Aruba CX 10000-48Y6C Power to Port (BF) AC Power Supply Unit (R8R52A)
n
A red-colored power supply release latch indicates a Port-to-Power air flow. A blue-colored power supply
release latch indicates a Power-to-Port air flow.
n
Power supply air flow direction must match.