PST & PSS & PSH SERIES PROGRAMMABLE POWER SUPPLY
PROGRAMMER MANUAL
29
Examples :
:OUTPut:COUPle:TRACking
2 set the output of the channel 1 and
channel 2 to series -tracking mode.
If the output is in the parallel-tracking mode, the command of
OUTPut:COUPle:TRACking?
will return the value of 1.
OUTPut:PROTection:CLEar
(no query form)
Function:
Clear all the protective messages (OTP, OVP, OCP) from the panel of
the device.
Syntax:
OUTPot:PROTection:CLEar
When the panel displays the protective message, no further setting can be
accepted by the device. Uses this command to clear the displayed
m essages in order to execute further setting.
Examples :
OUTPot:PROTection:CLEar
OUTPut:STATe
Function:
Set the output state on or off.
Syntax:
OUTPut:STATe <Boolean>
OUTPut:STATe?
<Boolean> can be 0(OFF) or 1(ON).
Returns:
0|1
PST & PSS & PSH SERIES PROGRAMMABLE POWER SUPPLY
PROGRAMMER MANUAL
30
Examples :
OUTPut:STATe 1 enabl es the power supply output.
If the power supply output is disabled, OUTPut:STATe? will return 0.
STATus:OPERation:CONDition?
(query only)
Function:
Return the contents of the OPERation register. The programmable power
supplies, however, do not use the OPERation register to report any
conditions.
Syntax:
STATus:OPERation:CONDition?
Returns:
<NR1>
Examples :
STATus:OPERation:CONDition?
returns 0.
STATus:OPERation:ENABle
Function:
Set or query the enable mask that allows the masked conditions in the
event register to be reported in the summary bit. If a bit is 1 (true) in the
enable register and its associated event bit changes to 1 (true), the
associated summary bit will change to 1 (true). Even though this is a
16-bit register, only 15 bits (bit 0 through bi t 14) are used. Bit 15 always
reads 0.
Syntax
STATus:OPERation:ENABle <NR 1>
STATus:OPERation:ENABle?
<NR 1>
is an integer from 0 to 32767.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com