Installation and operation manual

DPC200-R

airflow / pressure controller

Low pressure sensor with PI-control-mode and relay output

Doc.-no.: DPC200-R_02_EN

Issue: 06/2018

Summary of Contents for DPC200-R

Page 1: ...Installation and operation manual DPC200 R airflow pressure controller Low pressure sensor with PI control mode and relay output Doc no DPC200 R_02_EN Issue 06 2018 ...

Page 2: ...e de www sensor store de 06 2018 DPC200 R_02_EN This documentation including all parts is protected by copyright Any utili sation or modification other than permissible under the strict limitations of copyright law is prohibited and liable to prosecution without the approval of the Arthur Grillo GmbH This applies in particular to duplications trans lations microfilming and storage and processing i...

Page 3: ...ions 3 2 Wall mounting 4 Start up 4 1 Overview DPC200 R 4 2 Schematic view inside 4 3 Pressure connections 4 4 Electrical connection 4 5 Zero adjustment 5 Operation 5 1 Start menu 5 2 Menu structure 5 3 Measuring mode 5 4 Control mode 5 5 Adjustable parameters 5 6 Threshold calculation 5 7 Function relay alarm output 6 Maintenance 7 Warranty 8 Troubleshooting 9 Disposal 10 Specifications 10 1 CE l...

Page 4: ...o material damage or minor or moderate bodily injuries CAUTION 1 2 Used pictograms and symbols In this manual the following symbols are used General hazard symbol dan ger warning caution Signal word for important information regarding the product which needs to be specifically pointed out NOTICE Hazard word Type of hazard Hazard source Hazard prevention 1 3 General notes This manual contains infor...

Page 5: ...ble of the PI control 2 3 Functional description A soft silicone diaphragm is used as sensor Under the influence of the differential pressure the diaphragm displaces a measuring spring until the spring force compensates for the pressure pushing on the diaphragm A contactless differential transformer and suitable electronics convert this displacement into a continuously variable output voltage sign...

Page 6: ...ead the manual carefully before installation and operation Only experienced stuff may connect the device and bring it into operation CAUTION 3 1 Dimensions All dimensions in mm The device is position depended The DPC200 R must be mounted vertically The DPC200 R can be attached to a wall NOTICE 3 2 Wall mounting 1 Hold the DPC200 R against the wall Mark the mounting holes 2 Drill mounting holes for...

Page 7: ...land M16 x 1 5 3 Pressure connection 1 4 Pressure connection 2 5 Cable gland M16 x 1 5 1 2 3 4 5 4 2 Schematic view inside Button T1 and T2 serve for the operation of the menu 4 3 Pressure connections Connect all pressure connections properly with plastic tubing inner diameter 5 or 6 mm ButtonT1 ButtonT2 ...

Page 8: ... offset can be zeroed from the outside with a small bar magnet Do not use buttons T1 or T2 Adjustment Remove the tubing from the pressure connections Hold the bar magnet N S as shown here to the zero point adjustment for a short period of time to activate an internal reed switch The new zero point will be displayed and stored 5 Operation 5 1 Start menu For operating the menu unscrew the front cove...

Page 9: ...9 Doc no DPC200 R_02_EN Issue 06 2018 OPERATION 5 2 Menu structure ...

Page 10: ...e Press button T2 to get to the next menu item alarm delay time Switching delay time adjustment range 1 60 seconds or 2 15 minutes back and confirm Press button T1 to leave the menu Press button T2 to stay in the menu If selected parameter volume flow than follows the additional input for the k factor fan k factor k 70 Button T1 reset value Button T2 set value Button T1 confirm value display flash...

Page 11: ...ext menu item output voltage U 10 0V DC Button T1 reset value Button T2 set value Button T1 confirm value display flashes once Press button T2 to get to the next menu item P parameter 50 Button T1 reset value Button T2 set value Button T1 confirm value display flashes once Press button T2 to get to the next menu item l parameter 3 15 Button T1 reset value Button T2 set value Button T1 confirm valu...

Page 12: ...e 2000 Pa k 10 000 Vmax 447 214 m3 h Measuring range 4000 Pa k 10 000 Vmax 632 456 m3 h Measuring range 6000 Pa k 10 000 Vmax 774 597 m3 h K 70 Limit values Differential pressure from 0 up to 100 of measuring range Volume flow from 0 5 up to 100 of measuring range k factor is considered Please refer to chapter 5 6 OFF Nominal values setpoints Differential pressure from 0 up to 100 of measuring ran...

Page 13: ...h is betweenV_min andV_max and adjustable by our DPC200 R 0 1000 Pa 5 7 Function relay alarm output The DPC200 R has an relay alarm output depending on the operating mode the func tion is different In state of alarm the relay switches and is with 250Vac 10A loadable You can reach the relay via the connection terminal three four and five During alarm state in the control mode measuring mode an excl...

Page 14: ...heck electrical connection Measurement stays zero Function test with a slight pressure increase in measu ring mode for differential pressure Measuring error Perform zeroing as described in chapter 4 5 Error remains Contact manufacturer Display shows The device is in the alarm state see section 5 7 WARRANTY SUPPORT Measuring mode For limit value monitoring a limit value can be entered This value is...

Page 15: ...rt gases Silicon diaphragm with spring and differential transformer 0 50 Pa 0 6000 Pa 0 2 bar max 0 2 bar tubing 5 mm ø or 6 mm ø UL 94 HB Case polyamid cover ABS cable inlet M16x1 5 screw terminal Electronic protection against reversed polarization 20 30Vdc 24Vac 15 approx 10 mA 24Vdc and approx 20 mA with relay 0 10V Imax 0 4 mA 10Vdc Imax 2 mA 20Vdc Relay 250Vac 10 A LCD Display 2 x16 character...

Page 16: ... 03 correction 1 2011 06 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity for industrial environments DIN EN 61000 6 3 2011 09 Electromagnetic compatibility EMC Part 6 3 Generic standards Emission standard for residential commer cial and light industrial environments You can order the Declaration of Conformity at Arthur Grillo GmbH Am Sandbach 7 40878 Ratingen Phone 0 21 02 47...