The cooling subsystem is compliant to CP-TA B.4. The cooling system provides for greater than
40 CFM for the front blade and 5.0 CFM for the RTM.
The actual cooling performance depends on the slot population and the heat sink design of
installed blades and should be validated based on the used configuration.
The cooling subsystem provides greater than 24 CFM in the front slots in the presence of any
single fan failure.This exceeds the CP-TA B.4 specification.
3.2.7
Acoustic Noise Control
The system can generate a lot of acoustic noise. This system has a built-in noise control due to
the fan speed control. If the system is installed in an environment where the noise may be
harmful to personnel being exposed to the noise during extended time periods, additional
protective measures should be considered.
The distance to other equipment must be sufficient to avoid an overheating of the system.
Summary of Contents for AXP640
Page 1: ...AXP640 Installation and Use P N 6806800M24F May 2014 ...
Page 8: ...AXP640 Installation and Use 6806800M24F Contents 8 Contents Contents ...
Page 10: ...AXP640 Installation and Use 6806800M24F 10 List of Tables ...
Page 50: ...Platform Architecture AXP640 Installation and Use 6806800M24F 50 ...
Page 70: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24F 70 Figure 2 14 AC Inlet 220V ...
Page 101: ...Site Preparation AXP640 Installation and Use 6806800M24F 101 Figure 3 13 Planning Checklist 2 ...
Page 102: ...Site Preparation AXP640 Installation and Use 6806800M24F 102 ...
Page 112: ...AXP640 Operations AXP640 Installation and Use 6806800M24F 112 ...
Page 136: ...AXP640 Shelf Installation AXP640 Installation and Use 6806800M24F 136 ...
Page 164: ...FRU Installation AXP640 Installation and Use 6806800M24F 164 ...
Page 186: ...Shelf Management Alarm Module AXP640 Installation and Use 6806800M24F 186 ...
Page 189: ......