FRU Installation
AXP640 Installation and Use (6806800M24F
)
156
6. Open the ejector handle and gently pull on the PEM module. You will feel the PEM
disconnect from the backplane.
7. Pull the module straight out from the rail guides, about 12 inches.
6.4.3
Installation Procedure
To install a power entry module, follow the steps below:
1.
If not already removed, remove the front bezel by squeezing the retention clasps
incorporated into the top corners of the bezel and rotating the top of the bezel
away from the chassis.
2.
Insure the replacement PEM circuit breaker is in the open position.
3.
Align the PEM with the guide rails on the power bay that the PEM will be inserted
into.
4. Slide the module straight in on the guide rails, about 12 inches. You will feel the
PEM engage the backplane connector.
5. Secure the PEM with the chassis retention screw at the top of the PEM module.
6. Rotate the PEM handle down so that it is flush with the front of the PEM module.
7. Close the PEM circuit breaker.
8. Remove the lock and tagout from the circuit breakers on the branch circuit or
power distribution unit, and return power to the appropriate chassis power feed.
The DC PEMs will only engage a backplane connector in power bay A2 and B1 (PBA2 and
PBA1) Power bay A1 and B2 (PBA1 and PBB2) are required to have power bay slot fillers
installed.
Summary of Contents for AXP640
Page 1: ...AXP640 Installation and Use P N 6806800M24F May 2014 ...
Page 8: ...AXP640 Installation and Use 6806800M24F Contents 8 Contents Contents ...
Page 10: ...AXP640 Installation and Use 6806800M24F 10 List of Tables ...
Page 50: ...Platform Architecture AXP640 Installation and Use 6806800M24F 50 ...
Page 70: ...AXP640 Shelf Description AXP640 Installation and Use 6806800M24F 70 Figure 2 14 AC Inlet 220V ...
Page 101: ...Site Preparation AXP640 Installation and Use 6806800M24F 101 Figure 3 13 Planning Checklist 2 ...
Page 102: ...Site Preparation AXP640 Installation and Use 6806800M24F 102 ...
Page 112: ...AXP640 Operations AXP640 Installation and Use 6806800M24F 112 ...
Page 136: ...AXP640 Shelf Installation AXP640 Installation and Use 6806800M24F 136 ...
Page 164: ...FRU Installation AXP640 Installation and Use 6806800M24F 164 ...
Page 186: ...Shelf Management Alarm Module AXP640 Installation and Use 6806800M24F 186 ...
Page 189: ......