4-10
CHP Max™ Headend Optics Platform Chassis, Controllers and Power Supplies
Rev D
Setting Major and Minor Alarm Threshold Limits
The alarm parameters listed in Table 4.4 have four adjustable alarm thresholds and a fixed
deadband value associated with each parameter. Alarms generated by the status monitoring
circuit are based on which thresholds have been exceeded. Figure 4.7 shows the four
threshold levels and the corresponding alarms.
Figure 4.7
Threshold/Alarm
Diagram
The factory-default threshold and deadband values for each parameter are listed in
Table 4.4. A deadband or hysteresis value prevents alarm oscillation. Once a threshold is
exceeded, the alarm can only be downgraded if the parameter is at least a deadband below
the threshold value.
Table 4.4 Factory-default Threshold and Deadband Values
Parameter
Major
Low
Minor
Low
Nomina
l
Minor
High
Major
High
Deadband
+12 V
DC
Output
11.6
11.8
12.25
12.7
12.8
1
+5 V
DC
Output
4.7
4.9
5.25
5.6
5.7
1
+3.3 V
DC
Output
3.3
3.4
3.6
4.0
4.1
1
–5 V
DC
Output
–5.6
–5.4
–5.1
–4.7
–4.5
1
Fan 1 and 2 Current
CHP-PS/AC1 (mA)
149
150
275
449
450
1
CHP-PS/AC1-Q (mA)
59
61
85
448
450
1
CHP-PS/AC1-Q-NP (mA)
59
61
85
448
450
1
Internal Temperature (°C)
0
15
43
80
85
1
Major High
Minor High
Minor Low
Major Low
Threshold
No Alarm (green)
Major (red)
Minor (yellow)
Alarm
Major (red)
Minor (yellow)
Summary of Contents for CHP Max5000
Page 2: ......
Page 12: ...x CHP Max Headend Optics Platform Chassis Controllers and Power Supplies 1508685 Rev D...
Page 100: ...4 18 CHP Max Headend Optics Platform Chassis Controllers and Power Supplies Rev D...
Page 120: ...5 20 CHP Max Headend Optics Platform Chassis Controllers and Power Supplies Rev D...
Page 199: ...Rev D System Management Module 2 SMM 2 7 33 Figure 7 28 Add CHPMax5000 Device Window...
Page 261: ...1508685 Rev D CHP Max Trap Information B 29...
Page 262: ...B 30 CHP Max Headend Optics Platform Chassis Controllers and Power Supplies 1508685 Rev D...
Page 266: ......