Appendix A: Configuration presets
80
1X-E4 Series Installation Manual
Operating mode presets
NEN 2575 4E presets
Table 38: Configuration presets
Preset
41
Control panel
Four evacuation areas
EOL type
Passive
Output type
Class B
Evacuation sounder outputs
4
Fire routing outputs
2
Zone type
Odd: Automatic
Even: Manual
Table 39: Inputs and outputs
Input/Output Standard
EN 54-13
[1]
INPUT1
Fire routing inhibit delay
Fire routing acknowledge type
INPUT2
Delays off
Fault warning open supervision
OUT1
Sounder circuit (activated by a fire
alarm in zone 1)
Sounder circuit (activated by a fire
alarm in zone 1)
OUT2
Sounder circuit (activated by a fire
alarm in zone 2)
OUT3
Sounder circuit (activated by a fire
alarm in zone 3)
Sounder circuit (activated by a fire
alarm in zone 2)
OUT4
Sounder circuit (activated by a fire
alarm in zone 4)
OUT5
Fire routing ( activated by a automatic
fire alarm device)
Fire routing (activated by automatic or
manual fire alarm device)
OUT6
Fire routing (activated by a manual fire
alarm device)
[1] In this mode, EN 54-13 requires an additional 2010-1SB expansion board, configured with four
separate outputs. An alarm in zone 3 will activate output 1 and output 2. An alarm in zone 4 will
activate output 3 and output 4.
Summary of Contents for 1X-E4 Series
Page 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Page 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Page 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Page 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...