Chapter 2: Installation
1X-E4 Series Installation Manual
21
Connecting alarm and fault relays
Connect the alarm and fault equipment to the ALARM and FAULT relays.
Each potential-free relay output is activated in an alarm or fault situation
respectively. The fault relay output is activated (a short circuit between the
common (C) and normally closed (NC) terminals of the relay) when there is no
fault.
The maximum contact rating for each relay circuit is 2 A at 30 VDC.
Connecting expansion boards
Caution:
Risk of equipment damage. Always disconnect the control panel from
the mains power supply before installing an expansion board.
See your expansion board installation sheet for detailed installation information.
Connecting a fire network
Note:
See the
2010-1-NB Network Board Installation Sheet
for detailed
installation and connection information.
Each 2010-1-NB network board has two ports. Each port is connected (point to
point) to the corresponding ports of the network board in another control panel.
Figure 13: Network board connections
Two wiring options are possible:
• Ring configuration
• Bus configuration