Chapter 3: Configuration and commissioning
44
1X-X3E Series Installation Manual
Safety door fault delay
Use this menu to configure a delay from 10 to 90 seconds (in steps of 5 seconds)
in reporting safety door faults caused by incorrect status (open or closed). The
default setting is 30 seconds.
To configure a safety door delay:
1. Set the display as shown below, and then press Enter.
The Door Fault/Disabled LED flashes fast to indicate that the delay
configuration menu is active.
2. Select a delay value from 10 to 90 seconds using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Pressure switch type
Use this menu to configure the low pressure switch for detection of the container
pressure. Correct pressure can be either normally closed (NC) or normally open
(NO). The default setting is normally closed (NC).
To configure the pressure switch type:
1. Set the display as shown below, and then press Enter.
The Low Pressure LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Operates as normally closed (NC).
Operates as normally open (NO).
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......