![Aritech 1 3E Series Installation Manual Download Page 44](http://html.mh-extra.com/html/aritech/1-3e-series/1-3e-series_installation-manual_2972001044.webp)
Chapter 3: Configuration and commissioning
38
1X-X3E Series Installation Manual
Once configured the delay must be enabled at the operator user level.
To enable a configured delay:
1. Exit the installer user level.
2. Enter the operator user level password.
3. Press the Fire Routing Delay button.
A steady Fire Routing Delay LED indicates that the delay is enabled.
Fire delay operation
Delays can be configured for fire sounders and for fire routing. These delays will
only be applied when all of the following are true:
• The configured delay has been enabled
• The initiating device is a detector or a manual call point installed in an
automatic zone or the initiating device is a detector installed in a mixed zone
• The initiating device is in a zone configured for delays (the default
configuration)
If any of the above points are not true, then the control panel activates the fire
sounders and fire routing immediately after the detection of the fire alarm.
Sounder delays are bypassed when the alarm is detected in an extinguishing
zone.
Adding expansion boards
To add an expansion board to the system you must install the board and then
configure the system. See the expansion board’s installation guide for installation
instructions. See “Expansion board configuration” on page 62 for configuration
instructions.
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......