6.5. Reassembling the valve:
1.
Make sure that all the valve's components are in good condition, clean and free from sediments.
2.
Check the diaphragm for any wear and tear; if necessary replace it with a new one.
3.
Make sure that the finger-filter is clean.
4.
Reassemble the valve in reverse order of the above described disassembling steps.
5.
While reassembling the valve, make sure that the bonnet is evenly seated and tightened in all directions, parallel to the
valve's body.
6.6. Reassembling the Control loop:
1.
Make sure that all the control loop components are in good condition and clean.
2.
Clean the control tubing entry holes.
3.
Reassemble the control loop in reverse order of the above described disassembling steps.
6.7. Recommendation:
Replacement of the diaphragm and some internal parts is recommended after about three years of
operation, please see chapter
6
for instructions:
1.
Remove the cover of the valve.
2.
Clean the valve body from sediments.
3.
Clean the control tubing entry holes.
4.
Install a new Diaphragm and Elastomers.