![ARI Eliptix R-30ME Installation, Operating, Maintenance Download Page 10](http://html1.mh-extra.com/html/ari/eliptix-r-30me/eliptix-r-30me_installation-operating-maintenance_2969554010.webp)
R-30 ME
2.4. Initial Set-up - The ON/OFF Application
1.
The following is a general description of the ON/OFF Application:
This ON/OFF Electrically Operated Valve is an automatic control valve designed to be opened and closed by an
electrical command sent to its solenoid valve by an external controller.
The valve can be controlled either by a Normally Open (N.O.) or Normally Close (N.C.) solenoid.
For N.O. valve when the solenoid is energized water from the valve's upstream port flows into the control
chamber and the valve closes. When the solenoid is de-energized water from the control chamber is released to
the atmosphere and the valve fully opens.
For N.C. valve when the solenoid is energized water from the control chamber is released to the atmosphere and
the valve opens. When the solenoid is de-energized upstream water from the valve's upstream port flows into the
control chamber and the valve closes.
No.
Description
QTY.
1
Main Valve
1
2
Finger filter
1
3
Manual selector, ball valve,
3
-Way
1
4
Solenoid valve,
3
-Way
1
5
Solenoid manual override lever
1
Summary of Contents for Eliptix R-30ME
Page 18: ...R 30 ME 7 DIMENSIONAL DRAWING...
Page 19: ...R 30 ME 8 SOLENOIDS DATASHEETS...
Page 20: ...R 30 ME...