Technical Guide
P92x/EN CM/E11
Commissioning Guide
MiCOM P921-P922-P923
Page 13/28
ab
c
d
4.2.6
Rear communications port
This test should only be performed where the relay is to be accessed from a remote
location and will vary depending on the communications standard being adopted.
It is not the intention of the test to verify the operation of the complete system from the
relay to the remote control centre, just the relay's rear communications port and any
protocol converter necessary.
The protocol available for remote communication appears on the label on the relay
front panel (under the top cover).
4.2.6.1
Courier communications
If a K-Bus to RS232 KITZ protocol converter is installed, connect a portable PC
running the appropriate software to the incoming (remote from relay) side of the
protocol converter.
If a KITZ protocol converter is not installed, it may not be possible to connect the PC
to the type installed. In this case a KITZ protocol converter and portable PC running
appropriate software should be temporarily connected to the relay’s K-Bus port. The
terminal numbers for the relay’s K-Bus port are given in Table 5. However, as the
installed protocol converter is not being used in the test, only the correct operation of
the relay’s K-Bus port will be confirmed.
Connection
Terminal
KBUS
Modbus or VDEW
Screen
Screen
30
1
positive
31
2
negative
32
TABLE 5 : RS485 TERMINALS
The relay's Courier address in the "COMMUNICATIONS" menu must be set to a value
between 1 and 255.
Check that communications can be established with this relay using the portable PC.
4.2.6.2
Modbus communications
Connect a portable PC (“master station”) running the appropriate Modbus Master
Station software to the relay’s RS485 port via a RS485 to RS232 interface converter.
The terminal numbers for the relay’s RS485 port are given in Table 5.
Ensure that the relay address, baud rate and parity settings in the Modbus software
are set the same as on the MiCOM relay (see "COMMUNICATIONS" menu).
Check that communications with this relay can be established.
4.2.6.3
IEC60870-5-103 (VDEW) communications
IEC60870-5-103/VDEW communication systems are designed to have a local Master
Station. This should be used to verify that the relay's fibre optic or RS485 port, as
appropriate, is working.
Ensure that the relay address, baud rate and parity settings in the Master Station
software are set the same as on the MiCOM relay (see "COMMUNICATIONS" menu).
Check that, using the Master Station, communications with the relay can be
established.
Summary of Contents for MiCOM P921
Page 1: ...MiCOM P921 P922 P923 Voltage and Frequency Relays Technical guide P92x EN T E11...
Page 2: ......
Page 4: ...P92x EN T00 E11 Technical Guide Content Page 2 2 MiCOM P921 P922 P923 BLANK PAGE...
Page 5: ...Technical Guide Px2xx EN SS A11 SAFETY SECTION SAFETY SECTION...
Page 6: ......
Page 8: ...Px2xx EN SS A11 Technical Guide SAFETY SECTION Page 2 6 BLANK PAGE...
Page 12: ...Px2xx EN SS A11 Technical Guide SAFETY SECTION Page 6 6 BLANK PAGE...
Page 13: ...Technical Guide P92x EN GS E11 MiCOM P921 P922 P923 aBCD Getting Started...
Page 14: ......
Page 16: ...P92x EN GS E11 Technical Guide Getting Started Page 2 18 MiCOM P921 P922 P923 aBCD BLANK PAGE...
Page 33: ...Technical Guide P92x EN CO E11 MiCOM P921 P922 P923 aBCD Connection Diagrams...
Page 34: ......
Page 45: ...Technical Guide P92x EN TD E11 MiCOM P921 P922 P923 Technical Data...
Page 46: ......
Page 50: ...P92x EN TD E11 Technical Guide Technical Data Page 4 30 MiCOM P921 P922 P923 BLANK PAGE...
Page 76: ...P92x EN TD E11 Technical Guide Technical Data Page 30 30 MiCOM P921 P922 P923 BLANK PAGE...
Page 77: ...Technical Guide P92x EN FT E11 MiCOM P921 P922 P923 User Guide...
Page 78: ......
Page 190: ......
Page 258: ...P92x EN CT E11 Technical Guide Courier Database Page 68 118 MiCOM P921 P922 P923 BLANK PAGE...
Page 296: ...P92x EN CT E11 Technical Guide Courier Database Page 106 118 MiCOM P921 P922 P923 BLANK PAGE...
Page 298: ...P92x EN CT E11 Technical Guide IEC 60870 5 103 Page 108 118 MiCOM P921 P922 P923 BLANK PAGE...
Page 308: ...P92x EN CT E11 Technical Guide IEC 60870 5 103 Page 118 118 MiCOM P921 P922 P923 BLANK PAGE...
Page 309: ...Technical Guide P92x EN IN E11 MiCOM P921 P922 P923 abcd Installation...
Page 310: ......
Page 312: ...P92x EN IN E11 Technical Guide Installation Page 2 10 MiCOM P921 P922 P923 abcd BLANK PAGE...
Page 319: ...P92x EN IN E11 Technical Guide Installation Page 10 10 MiCOM P921 P922 P923 abcd BLANK PAGE...
Page 320: ...Technical Guide P92x EN CM E11 MiCOM P921 P922 P923 abcd Commissioning Guide...
Page 321: ......
Page 351: ...Technical Guide P92x EN RS E11 MiCOM P921 P922 P923 Test Report...
Page 352: ......
Page 354: ...P92x EN RS E11 Technical Guide Test Report Page 2 22 MiCOM P921 P922 P923 BLANK PAGE...
Page 375: ......