Instruction manual
–
AQ G3x7 Generator protection IED
9 (211
)
3
S
OFTWARE SETUP OF THE
IED
In this chapter are presented the protection and control functions as well as the monitoring
functions.
The implemented protection functions are listed in the table. The function blocks are
described in details in following chapters.
Table 3-1 Available protection functions for AQ G357 IED
Name
IEC
ANSI
Description
DIF87
3IdG>
87G
Generator differential protection
IOC50
I>>>
50
Three-phase instantaneous overcurrent protection
TOC50_low
TOC50_high
I>
I>>
51
Three-phase time overcurrent protection
IOC50N
I0>>>
50N
Residual instantaneous overcurrent protection
TOC51N_low
TOC51N_high
I0>
I0>>
51N
Residual time overcurrent protection
VOC51
Iv>
51V
Voltage restrained or voltage controlled overcurrent
protection
TOC67_low
TOC67_high
IDir>
IDir>>
67
Directional three-phase overcurrent protection
TOC67N_low
TOC67N_high
I0Dir>
I0Dir>>
67N
Directional residual overcurrent protection
INR2
I2h >
68
Inrush detection and blocking
TOC46
I2
46
Negative sequence overcurrent
VCB60
Iub >
60
Current unbalance protection
TTR49L
T >
49
Thermal protection
TOV59_low
TOV59_high
U >
U >>
59
Definite time overvoltage protection
TUV27N_low
TUV27N_high
U <
U <<
27
Definite time undervoltage protection
TOV59N_low
TOV59N_high
U0>
U0>>
59N
Residual voltage protection
TOV64F3
U0f3>
64F3
100% stator earth fault protection
TOF81_high
TOF81_low
f >
f >>
81O
Overfrequency protection
TUF81_high
TUF81_low
f <
f <<
81U
Underfrequency protection
FRC81_high
FRC81_low
df/dt
81R
Rate of change of frequency protection
DOP32
P>
32
Reverse power / directional overpower protection
DUP32
P<
32
Directional underpower protection