7.4
H
ARDWARE
7.4.1
P
OWER SUPPLY MODULE
Rated voltage
80-300Vac/dc
Maximum interruption
100ms
Maximum power consumption
30W
7.4.2
C
URRENT MEASUREMENT MODULE
Nominal current
1/5A (parameter settable)
0.2A (ordering option)
Number of channels per module
4
Rated frequency
50Hz
60Hz (ordering option)
Burden
<0.1VA at rated current
Thermal withstand
20A (continuous)
500A (for 1s)
1200A (for 10ms)
Current measurement range
0-50xIn
7.4.3
V
OLTAGE MEASUREMENT MODULE
Rated voltage Un
100/√3, 100V, 200/√3, 200V
(parameter settable)
Number of channels per module
4
Rated frequency
50Hz
60Hz (ordering option)
Burden
<1VA at 200V
Voltage withstand
250V (continuous)
Voltage measurement range
0.05-1.2xUn
7.4.4
H
IGH SPEED TRIP MODULE
Rated voltage Un
110/220Vdc
Number of outputs per module
4
Continuous carry
8A
Making capacity
30A (0.5s)
Breaking capacity
4A (L/R=40ms, 220Vdc)