Instruction manual
–
AQ G3x7 Generator protection IED
201 (211
)
Residual overvoltage protection function U0>, U0>> (59N)
Pick-up starting inaccuracy
< 0,5 %
Reset time
U>
→
Un
U>
→ 0
50 ms
40 ms
Operate time inaccuracy
+ 15 ms
7.1.4
F
REQUENCY PROTECTION FUNCTIONS
Overfrequency protection function f>, f>>, (81O)
Operating range
40 - 60 Hz
Operating range inaccuracy
30mHz
Effective range inaccuracy
2mHz
Minimum operating time
100ms
Operation time inaccuracy
+ 10ms
Reset ratio
0,99
Underfrequency protection function f<, f<<, (81U)
Operating range
40 - 60 Hz
Operating range inaccuracy
30mHz
Effective range inaccuracy
2mHz
Minimum operating time
100ms
Operation time inaccuracy
+ 10ms
Reset ratio
0,99
Rate of change of frequency protection function df/dt>, df/dt>> (81R)
Effective operating range
-5 - +5Hz/sec
Pick-up inaccuracy
0,01Hz/sec
Minimum operating time
100 ms
Operation time inaccuracy
+ 15ms
7.1.5
O
THER PROTECTION FUNCTIONS