Instruction manual
–
AQ G3x7 Generator protection IED
178 (211
)
Binary status signal
Explanation
DRE_Start_GrO_
Output status of a graphic equation defined by the user to start
the disturbance recorder function.
Table 3-83: The binary input signal of the disturbance recorder function
Table 3-84Setting parameters of the disturbance recorder function
Parameter
Setting value, range
and step
Description
Operation
On, Off
Function enabling / disabling. Default setting is On
PreFault
50...500 ms by step
of 1 ms
Pre triggering time included in the recording. Default setting
is 200 ms.
PostFault
50...1000 ms by step
of 1 ms
Post fault time included in the recording. Default setting is
200 ms.
MaxFault
200...5000 ms by
step of 1 ms
Overall maximum time limit in the recording. Default setting
is 1000 ms.
3.3.8
E
VENT RECORDER
The events of the device and those of the protection functions are recorded with a time
stamp of 1 ms time resolution. This information with indication of the generating function
can be checked on the touch-
screen of the device in the “Events” page, or using an Internet
browser of a connected computer.
Table 3-85 List of events.
Event
Explanation
Voltage transformer supervision function (VTS)
VT Failure
Error signal of the voltage transformer supervision function
Common
Mode of device
Mode of device
Health of device
Health of device
Three-phase instantaneous overcurrent protection function (IOC50)
Trip L1
Trip command in phase L1
Trip L2
Trip command in phase L2
Trip L3
Trip command in phase L3
General Trip
General trip command
Residual instantaneous overcurrent protection function (IOC50N)
General Trip
General trip command
Directional overcurrent protection function (TOC67) low setting stage
Start L1
Start signal in phase L1