Instruction manual
–
AQ G3x7 Generator protection IED
158 (211
)
Parameter
Setting value, range
and step
Description
Operation
Off
Current
Contact
Current/Contact
Operating mode selection for the function. Operation can be
either disabled “Off” or monitoring either measured current or
contact status or both current and contact status. Default
setting is “Current”.
Start current
Ph
20…200 % by step of
1 %
Pick-up current for the phase current monitoring. Default
setting is 30 %.
Start current
N
10…200 % by step of
1 %
Pick-up current for the residual current monitoring. Default
setting is 30 %
Backup Time
Delay
60…1000 ms by step
of 1 ms
Time delay for CBFP tripping command for the back-up
breakers from the pick-up of the CBFP function monitoring.
Default setting is 200 ms.
Pulse length
0…60000 ms by step
of 1 ms
CBFP pulse length setting. Default setting is 100 ms.
3.2.26
I
NRUSH CURRENT DETECTION
INR2
(68)
The current can be high during transformer energizing due to the current distortion caused by
the transformer iron core asymmetrical saturation. In this case, the second harmonic content
of the current is applied to disable the operation of the desired protection function(s).
The inrush current detection function block analyses the second harmonic content of the
current, related to the fundamental harmonic. If the content is high, then the assigned status
signal is set to “true” value. If the duration of the active status is at least 25 ms, then the
resetting of the status signal is delayed by an additional 15 ms. Inrush current detection is
applied to residual current measurement also with dedicated separate function.
Table 3-67: Setting parameters of the inrush function
Parameter
Setting value, range
and step
Description
Operation
Off
Current
Contact
Current/Contact
Operating mode selection for the function. Operation can be
either disabled “Off” or monitoring either measured current or
contact status or both current and contact status. Default
setting is “Current”.
Start current
Ph
20…200 % by step of
1 %
Pick-up current for the phase current monitoring. Default
setting is 30 %.
Start current
N
10…200 % by step of
1 %
Pick-up current for the residual current monitoring. Default
setting is 30 %
Backup Time
Delay
60…1000 ms by step
of 1 ms
Time delay for CBFP tripping command for the back-up
breakers from the pick-up of the CBFP function monitoring.
Default setting is 200 ms.
Pulse length
0…60000 ms b
y step
of 1 ms
CBFP pulse length setting. Default setting is 100 ms.
3.3
C
ONTROL AND MONITORING FUNCTIONS
Name
IEC
ANSI
Description