Solid or stranded wire
Maximum wire diameter:
2.5mm
2
Phoenix Contact MSTB2,5-5,08
9.1.3.2. Binary output module
Table. 9.1.3.2. - 270. Binary output module technical data
Rated values
Rated auxiliary voltage
265V(AC/DC)
Continuous carry
5A
Make and carry 0.5s
Make and carry 3s
30A
15A
Breaking capacity, DC (L/R = 40 ms)
at 48VDC
at 110 VDC
at 220 VDC
1A
0.4A
0.2A
Control rate
5 ms
Settings
Polarity
Software settable: Normally On / Normally Off
Terminal block connection
Solid or stranded wire
Phoenix Contact MSTB2,5-5,08
Maximum wire diameter:
2.5mm
2
9.1.3.3. Arc protection module
Table. 9.1.3.3. - 271. Arc protection module technical data
Connections
Input arc point sensor
S1, S2, S3, S4 (pressure and light or light only)
Performance
Pick-up light intensity
8000, 25000 or 50000 Lux (sensor selectable in order code)
Inaccuracy
- Point sensor detection radius
180 degrees
Start and instant operating time (light only)
Typically <5 ms (dedicated semiconductor outputs)
Typically <10 ms (regular output relays)
Table. 9.1.3.3. - 272. High Speed Outputs (HSO1…2)
Rated values
Rated auxiliary voltage
250Vdc
Continuous carry
2A
Make and carry 0.5s
Make and carry 3s
15A
6A
Breaking capacity, DC (L/R = 40 ms)
1A / 110W
Control rate
5ms
Operation delay
<1ms
Polarity
Normally Off
Contact material
Semiconductor
Terminal block connection
AQ-F255
Instruction manual
Version: 2.00
341
© Arcteq Relays Ltd