6. Scan: Scan Slot E, if is empty goes to next slot. If found 8DI module then reserve to this slot
running number regard if Slot C was empty or had other than DIx module then DI4, DI5, DI6,
DI7, DI8, DI9, DI10 and DI11 or if Slot C has also DI8 module then DI12, DI13, DI14, DI15,
DI16, DI17, DI18 and DI19. If found DO5 module then reserve to this slot OUT6, OUT7, OUT8,
OUT9 and OUT10 or OUT11, OUT12, OUT13, OUT14 and OUT15 with similar basis than for
the inputs.
If found arc protection module, reserve sensor channels S1, S2, S3, S4, high speed outputs
HSO1, HSO2 and binary input channel ArcBI to this slot.
7-15 Scan: Similar operation to Scan 6.
In the previous example only IO add-on cards were described if installed into the option module slots. If
the slot has other type of module than IO they are treated similarly. For example, in case of added
communication port the upper port of the communication module shall be in minimum of Comm. port 3
etc. since in the CPU-module already exist Comm. ports 1 and 2. After communication port is detected
it is added into the communication space in the IED and corresponding settings are enabled for the
IED.
In the example case of AQ-X255-XXXXXXX-
BBBBBCAAAAJ
number of available binary input
channels is DI1…DI43, of which DI1-DI3 are in the CPU module and DI4-DI11 are in Slot C etc. All
available binary output channels are DO1…DO10, of which DO1-DO5 are in the CPU module and
DO6-DO10 are in slot I. If the con guration should differ from this example the same principle is always
applied into the IED. Slot N has “double ber ethernet” module installed.
8.2. CPU, IO and Power supply module
Figure. 8.2. - 199. Main processor module CPU, IO, communications and PSU with 3 digital inputs.
Connector
Description
COM A:
Communication port A, RJ-45. For Modbus TCP and station bus communications.
COM B:
Communication port B, RS-485. For Modbus RTU and IEC-103 SCADA communications. Pin-out starting from
the left: 1=DATA +, 2=DATA -, 3=GND, 4&5=Terminator resistor enabled by shorting.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
320