Arc point sensor inputs
Channels S1, S2, S3, S4 (pressure and light sensor, or light-only sensor)
Up to four (4) sensors per channel
System frequency operating range
6.00…75.00 Hz
Pick-up
Pick-up current setting (phase current)
Pick-up current setting (residual current)
Pick-up light intensity
0.50…40.00 × I
N
, setting step 0.01 × I
N
0.10…40.00 × I
N
, setting step 0.01 × I
N
8, 25 or 50 kLx (the sensor is selected in the order code)
Starting inaccuracy (IArc> and I0Arc>)
±3 % of the set pick-up value > 0.5 × I
N
setting. 5 mA < 0.5 × I
N
setting.
Point sensor detection radius
180 degrees
Operation time
Light only:
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 7 ms (3…12 ms)
Typically 10 ms (6.5…15 ms)
Light + current criteria (zone 1…4):
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 10 ms (6.5…14 ms)
Typically 14 ms (10…18 ms)
Arc BI only:
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 7 ms (2…12 ms)
Typically 10 ms (6.5…15 ms)
Reset
Reset ratio for current
97 % of the pick-up setting
Reset time
<35 ms
No
Notte!
e!
• The maximum length of the arc sensor cable is 200 meters.
9.2.1.21 Voltage memory
Table. 9.2.1.21 - 347. Technical data for the voltage memory function.
Measurement inputs
Voltage inputs
U
L1
, U
L2
, U
L3
U
L12
, U
L23
, U
L31
+ U
0
Current inputs (back-up frequency)
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Pick-up
Pick-up voltage setting
Pick-up current setting (optional)
2.00…50.00 %U
N
, setting step 0.01 x %U
N
0.01…50.00 × I
N
, setting step 0.01 × I
N
Inaccuracy:
- Voltage
- Current
±1.5 %U
SET
or ±30 mV
±0.5 %I
SET
or ±15 mA (0.10…4.0 × I
SET
)
Operation time
Angle memory activation delay
<20 ms (typically 5 ms)
Maximum active time
0.020…50.000 s, setting step 0.005 s
Inaccuracy:
- Definite time (U
M
/U
SET
ratio >1.05)
±1.0 % or ±35 ms
Angle memory
Angle drift while voltage is absent
±1.0° per 1 second
Reset
A
AQ
Q-F215
-F215
Instruction manual
Version: 2.04
476