Reset time setting
Inaccuracy: Reset time
0.000…150.000 s, step 0.005 s
±1.0 % or ±45 ms
Instant reset time and start-up reset
<50 ms
9.2.1.5 Intermittent earth fault protection (I0int>; 67NT)
Table. 9.2.1.5 - 331. Technical data for the intermittent earth fault function.
Measurement inputs
Current inputs (selectable)
Residual current channel I
01
(Coarse)
Residual current channel I
02
(Fine)
Current input magnitudes
Residual current samples
Voltage inputs (selectable)
Residual voltage from U3 or U4 voltage channel
Voltage input magnitude
Zero sequence voltage samples
Pick-up settings
Spikes to trip
1…50, setting step 1
Pick-up current setting
Pick-up voltage setting
0.05…40.00 × I
n
, setting step 0.001 × I
n
1.00…100.00 %U0
n
, setting step 0.01 %U0
n
Pick-up inaccuracy
Starting I01 (1 A)
Starting I02 (0.2 A)
Voltage U0
±0.5 %I0
set
or ±3 mA (0.005…10.0 x I
set
)
±1.5 %I0
set
or ±1.0 mA (0.005…25.0 x I
set
)
±1.0 %U0
set
or ±30 mV
Operation time setting
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Operation time inaccuracy
Definite time: I
m
/I
set
ratio 1.05
→
±1.0 % or ±30 ms
Instant operation time
Start time and instant operation time (trip):
- I
m
/I
set
ratio 1.05
→
<15 ms
Reset time
Reset time setting (FWD and REV)
Inaccuracy: Reset time
0.000…1800.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
9.2.1.6 Negative sequence overcurrent/ phase current reversal/ current unbalance
protection (I2>; 46/46R/46L)
Table. 9.2.1.6 - 332. Technical data for the current unbalance function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input calculations
Positive sequence current (I1)
Negative sequence current (I2)
Pick-up
Used magnitude
Negative sequence component I2pu
Relative unbalance I2/I1
Pick-up setting
0.01…40.00 × I
n
, setting step 0.01 × I
n
(I2pu)
1.00…200.00 %, setting step 0.01 % (I2/I1)
A
AQ
Q-F215
-F215
Instruction manual
Version: 2.04
465