9.2.2.2 Object control and monitoring
Table. 9.2.2.2 - 324. Technical data for the object control and monitoring function.
Signals
Input signals
Digital inputs
Software signals
Output signals
Close command output
Open command output
Operation time
Breaker traverse time setting
0.02…500.00 s, setting step 0.02 s
Max. close/open command pulse length
0.02…500.00 s, setting step 0.02 s
Control termination time out setting
0.02…500.00 s, setting step 0.02 s
Inaccuracy:
- Definite time operating time
±0.5 % or ±10 ms
Breaker control operation time
External object control time
<75 ms
Object control during auto-reclosing
See the technical sheet for the auto-reclosing function.
9.2.2.3 Auto-reclosing (0
→
1; 79)
Table. 9.2.2.3 - 325. Technical data for the auto-reclosing function.
Input signals
Input signals
Software signals (protection, logics, etc.)
Binary inputs
Requests
REQ1-5
5 priority request inputs; can be set parallel as signals to each request
Shots
1-5 shots
5 independent or scheme-controlled shots in each AR request
Operation time
Operating time settings:
- Lockout after successful AR
- Object close reclaim time
- AR shot starting delay
- AR shot dead time delay
- AR shot action time
- AR shot specific reclaim time
0.000…1800.000 s, setting step 0.005 s
0.000…1800.000 s, setting step 0.005 s
0.000…1800.000 s, setting step 0.005 s
0.000…1800.000 s, setting step 0.005 s
0.000…1800.000 s, setting step 0.005 s
0.000…1800.000 s, setting step 0.005 s
Inaccuracy
AR starting (from a protection stage's START signal)
±1.0 % or ±30 ms (AR delay)
AR starting (from a protection stage's TRIP signal)
Trip delay inac25 ms (Prot AR delay)
Dead time
±1.0 % or ±35 ms (AR delay)
Action time
±1.0 % or ±30 ms (AR delay)
Instant starting time
Instant operation time
Protection activation delay + 15 ms (Prot AR delay)
A
AQ
Q-F213
-F213
Instruction manual
Version: 2.04
445