Instruction manual –AQ F210 Feeder Protection IED
253 (292
)
Naming convention of the binary outputs provided by this module is presented in the chapter
6 Construction and installation.
For further details refer to the “Technical data” section of this document.
7.5
A
RC PROTECTION MODULE
(
OPTION
)
The arc protection module is an add-on module for four (4) light sensor channels. This module also
has two (2) high speed outputs and one (1) binary input. This module can be ordered directly as
factory installed option or it can be field upgraded if needed after the first installation of the AQ-200
series IED.
Connector Description
S1
Light sensor channels 1…4 with plus, sensor
and ground connectors.
S2
S3
S4
SlotX 1
HSO2 + NO
SlotX 2
Common b for HSO
SlotX 3
HSO1 + NO
SlotX 4
Arc BI1 + pole
SlotX 5
Arc BI1 - pole
Figure 7.5-7 Arc protection module for four light sensors, two high speed outputs and one
binary input.
In case any of sensor channels S1…S4 is not connected correctly it won’t work. Each channel
can have up to three light sensors connected on parallel. It is up to the user how many
channels are used.
High speed outputs HSO1 and HSO2 operate only with DC supply. Battery plus (+) has to be
wired according the drawing and output 1 or 2 NO side is wired trough trip coil to battery minus
(-). High speed output voltage withstand is up to 250VDC. For further information see the
technical data chapter of the manual. High speed output operation time is less than 1ms.