Connector
Description
X 5–6
OUTx + 3 (1
st
and 2
nd
pole NO)
X 7–8
OUTx + 4 (1
st
and 2
nd
pole NO)
X 9–10
OUTx + 5 (1
st
and 2
nd
pole NO)
The DO5 module is an add-on module with five (5) digital outputs. This module can be ordered directly
to be installed into the device in the factory, or it can be upgraded in the field after the device's original
installation when required. The properties of the outputs in this module are the same as those of the
outputs in the main processor module. The user can set the digital output controls with software. All
digital outputs are scanned in 5 ms program cycles, and their contacts are mechanical in type. The
rated voltage of the NO/NC outputs is 250 VAC/DC.
For the naming convention of the digital inputs provided by this module please refer to the chapter titled
"Construction and installation".
For technical details please refer to the chapter titled "Digital output module" in the "Technical data"
section of this document.
8.7 Dimensions and installation
The device can be installed either to a standard 19” rack or to a switchgear panel with cutouts. The
desired installation type is defined in the order code. When installing to a rack, the device takes a
quarter (¼) of the rack's width, meaning that a total of four devices can be installed to the same rack
next to one another.
The figures below describe the device dimensions (first figure), the device installation (second), and the
panel cutout dimensions and device spacing (third).
Figure. 8.7 - 253. Device dimensions.
A
AQ
Q-F205
-F205
Instruction manual
Version: 2.04
386
© Arcteq Relays Ltd
IM00013