Settings.
These settings can be accessed at
Control
→
Device I/O
→
Programmable control switch
.
Table. 5.5.5. - 98. Settings.
Name
Range
Default
Description
Switch name
-
Switchx
The user-settable name of the selected switch. The name can be up to
32 characters long.
Access level for
Mimic control
0: User
1: Operator
2:
Con gurator
3: Super
user
2:
Con gurator
Determines which access level is required to be able to control the
programmable control switch via the Mimic.
Events
The programmable control switch function (abbreviated "PCS" in event block names) generates events
from status changes. The user can select the status ON or OFF for messages in the main event
buffer. The function offers ve (5) independent switches.
Table. 5.5.5. - 99. Event codes.
Event number
Event channel
Event block name
Event code
Description
384
6
PCS
0
Switch 1 ON
385
6
PCS
1
Switch 1 OFF
386
6
PCS
2
Switch 2 ON
387
6
PCS
3
Switch 2 OFF
388
6
PCS
4
Switch 3 ON
389
6
PCS
5
Switch 3 OFF
390
6
PCS
6
Switch 4 ON
391
6
PCS
7
Switch 4 OFF
392
6
PCS
8
Switch 5 ON
393
6
PCS
9
Switch 5 OFF
5.6. Monitoring functions
5.6.1. Disturbance recorder (DR)
The disturbance recorder is a high-capacity (64 MB) and fully digital recorder integrated to the
protection relay. The maximum sample rate of the recorder's analog channels is 64 samples per cycle.
The recorder also supports 32 digital channels simultaneously with the twenty (20) measured analog
channels.
AQ-E215
Instruction manual
Version: 2.01
119