Reset time setting
Inaccuracy: Reset time
0.010…150.000 s, step 0.005 s
±1.0 % or ±35 ms
Instant reset time and start-up reset
<50 ms
9.2.1.20 Resistance temperature detectors
Table. 9.2.1.20 - 352. Technical data of the resistance temperature detectors.
Inputs
Resistance input magnitudes
Measured temperatures measured by RTD sensors
Alarm channels
12 individual alarm channels
Settable alarms
24 alarms available (two per each alarm channel)
Pick-up
Alarm setting range
Inaccuracy
Reset ratio
101.00…2000.00 deg, setting step 0.1 deg (either < or > setting)
±3 % of the set pick-up value
97 % of the pick-up setting
Operation
Operating time
Typically <500 ms
9.2.1.21 Arc fault protection (IArc>/I0Arc>; 50Arc/50NArc) (optional)
Table. 9.2.1.21 - 353. Technical data for the arc fault protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Residual current channel I
01
(Coarse)
Residual current channel I
02
(Fine)
Current input magnitudes
Sample-based phase current measurement
Sample-based residual current measurement
Arc point sensor inputs
Channels S1, S2, S3, S4 (pressure and light sensor, or light-only sensor)
Up to four (4) sensors per channel
System frequency operating range
6.00…75.00 Hz
Pick-up
Pick-up current setting (phase current)
Pick-up current setting (residual current)
Pick-up light intensity
0.50…40.00 × I
N
, setting step 0.01 × I
N
0.10…40.00 × I
N
, setting step 0.01 × I
N
8, 25 or 50 kLx (the sensor is selected in the order code)
Starting inaccuracy (IArc> and I0Arc>)
±3 % of the set pick-up value > 0.5 × I
N
setting. 5 mA < 0.5 × I
N
setting.
Point sensor detection radius
180 degrees
Operation time
Light only:
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 7 ms (3…12 ms)
Typically 10 ms (6.5…15 ms)
Light + current criteria (zone 1…4):
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 10 ms (6.5…14 ms)
Typically 14 ms (10…18 ms)
Arc BI only:
- Semiconductor outputs HSO1 and HSO2
- Regular relay outputs
Typically 7 ms (2…12 ms)
Typically 10 ms (6.5…15 ms)
Reset
Reset ratio for current
97 % of the pick-up setting
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
408
© Arcteq Relays Ltd
IM00035