5.2 Configuring Output Jumpers
23
5.1.2
List of Default Jumper Positions and Functions
Jumper
Function
Default Setting
JMP1
Antenna Preamp
Fixed (do not change)
JMP2
Event Input Connector
C - Event Panel
JMP3
Event Input Voltage
A, 5 to 12 Vdc
JMP4
Comm Port 1
A, Txd - ch
JMP5
Comm Port 1
B, DTR
JMP6
Comm Port 2
A, Txd - ch
JMP7
Comm Port 2
B, DTR
JMP8
Relay Mode (Form C Contacts)
A, Out Of Lock
JMP10
Timing Output 1
A, IRIG-B, unmodulated
JMP11
Timing Output 1
C, CMOS - 5 Vdc
JMP12
Timing Output 2
A, IRIG-B, unmodulated
JMP13
Timing Output 2
C, CMOS - 5 Vdc
JMP14
Timing Output 3
A, IRIG-B, unmodulated
JMP15
Timing Output 3
C, CMOS - 5 Vdc
JMP16
Timing Output 4
A, IRIG-B, unmodulated
JMP17
Timing Output 4
C, CMOS - 5 Vdc
Table 5.1: Default Mainboard Jumper Settings
NOTE:
Jumpers in the following tables are grouped according to main functions and not neces-
sarily in numerical order.
NOTE:
Values in tables marked with a “*” show the default positions.
5.2
Configuring Output Jumpers
The Model 1094B has four multifunction timing outputs that may be configured independently. To
configure any of the output jumpers, follow the steps enumerated below. Table 5.2 organizes the
four outputs in one table, since they are all configured in the same manner.