3.3 Option 10, 110 to 350 Vdc Terminal Power Strip, Surge Withstand
13
3.2.1
Option 08, Connecting Inlet Power
When wiring station batteries to this power supply, make sure to first connect an earth ground
wire to the terminal strip connector labeled “G” (for ground). Positive and Negative terminals
are marked on a label as “+” and “–”. After connecting a ground wire, connect the positive and
negative leads from the station batteries to the corresponding Option 08 terminals.
3.3
Option 10, 110 to 350 Vdc Terminal Power Strip, Surge With-
stand
This option replaces the standard IEC-320 inlet with a 3-pole terminal strip and provides inlet
surge protection for compliance with ANSI C37.90-1 and IEC 801-4. Input voltages are: 85 to 264
Vac, 47 to 440 Hz, or 110 to 350 Vdc,
<
20 VA typical.
Figure 3.3: Option 10 Power Supply Inlet Description
3.3.1
Option 10, Connecting Inlet Power
When wiring this power supply, make sure to first connect an earth ground wire to the terminal strip
connector labeled “G” (for ground). Positive and negative terminals are marked on the terminals
as “+” and “–”. After connecting a ground wire, connect the positive and negative leads to the
clock power inlet terminals. Lastly, connect the power inlet leads to the station batteries. When
using with AC inlet supplies, Positive is the same as Line and Negative is the same as Neutral.
3.4
Fuse Locations and Types
Use the fusing table below for identifying the correct fuse for your option power supply.
PS Option
Arbiter P/N
Fuse ID
Size, mm
07
FU0001816
F1AL250V
5 x 20
08
FU0001419
T2AL250V
5 x 20
10
FU0001816
F1AL250V
5 x 20
Table 3.2: Fuse Chart