AquaTelemetry Instruction Manual
10401-01193 Rev H
5. Requesting Data by SMS
5.1. Requesting Current Configuration (Will respond to any registered SMS number)
The current configuration can be requested at any time by sending the word CONFIG (or
CO for short) to the AquaTelemetry unit by SMS. This will result in a reply spanning two
SMS messages:
Message 1 contents
Brief explanation
SETTINGS UPDATE
Message heading
SITE = XXXXXXXXXXXXXXXX
Site identifier (default is unit's serial number)
TIME HH:MM
Daylight saving offset applied to the master clock
UPLD LOG EVERY=HH:MM
Log upload by email interval
FIRST UPLD AT=HH:MM
Time first log is uploaded by email each day
SMS CHK EVERY=HH:MM
Interval at which SMS messages are read
LOG INTERVAL=HH:MM
Normal data logging interval
Message 2 contents
Brief explanation
SETTINGS UPDATE
Message heading
SITE = XXXXXXXXXXXXXXXX
Site identifier (default is unit's serial number)
ALERT LOG INTERVAL=H:MM
Shorter logging interval when an alert is active
L1 ALERT =+XXXXX
Alert level 1 in mm
L2 ALERT =+XXXXX
Alert level 2 in mm
L3 ALERT =+XXXXX
Alert level 3 in mm
L4 ALERT =+XXXXX
Alert level 4 in mm
RATE ALERT=+XXXX
Rate of change alert in mm/minute
5.2. Requesting Current Level and Alert Status (Will respond to any number)
Once all the setup has been completed, the current water level, water temperature, rate of
change and alert status can be requested at any time by sending the word LEVEL (or LE
for short) to the AquaTelemetry unit by SMS.
This will result in a reply containing:
Level Message content
Brief explanation
SITE= XXXXXXXXXXXXXXX
Site identifier
LEVEL AT HH:MM DD/MMM/YY
Current time and date of reading
LEVEL=XX.XXXm
Current water level over sonde
TEMP=XX.XXC
Current sonde temperature
RATE= +XXXXmm/min
Rate of level change since last reading
ALERT= NONE (or LEVEL X or RATE)
Alert status
BATTERY=XX.XX V
Battery voltage
© 2020 Aquaread
®
Ltd.
www.aquaread.com
Page 27 of 34