VCS – Viscosity Controller
17
6
Troubleshooting
6.1
Controller problems and recommended actions
Problem
Possible causes
Recommended actions
Err 1...6
Fault on measuring input nr. …
check measuring lines
for short circuit or
breakage
check measuring input
by connecting a RTD
Err 55
Fault on loading the parameter;
press any key, the
controller starts in
emergency operation
mode,
configuration of the
parameters has to be
checked
Err 50
Hardware error in program section
no further operation
possible, remit
controller for repair
Err 52
Hardware error in data section
no further operation possible, remit controller for repair
no further operation
possible, remit
controller for repair
Err 58
Err 59
Err 60
Err 61
Binary inputs out of function (status = 0),
Digital outputs out of function (switched off),
Relay outputs out of function (switched off),
Analogue outputs out of function (0 %),
remit controller for
repair
Err 62
Err 63
Data connection to the modular fault detector 826..
interrupted,
Data connection to the hardware expansion modules
interrupted,
check cables
Error messages during self-adaptation:
Err 202
Ambient conditions are not suitable for self-adaptation;
adjust parameter
manually
Err 205
routine exceeded the setpoint
raise setpoint or lower
actual value and start
adaptation again
Err 206
Fault on measuring input during adaptation;
check the wiring and
start adaptation again
Summary of Contents for Viscosity VC312
Page 23: ...VCS Viscosity Controller 23 ...
Page 24: ...24 VCS Viscosity Controller ...
Page 25: ...VCS Viscosity Controller 25 ...
Page 26: ...26 VCS Viscosity Controller ...
Page 27: ...VCS Viscosity Controller 27 8 3 2 VC622 322 622 722 controller connection ...
Page 28: ...28 VCS Viscosity Controller ...
Page 29: ...VCS Viscosity Controller 29 ...
Page 30: ...30 VCS Viscosity Controller ...
Page 31: ...VCS Viscosity Controller 31 ...