Environmental Monitoring System (EMS-5 / 10) Instruction Manual
13
3.2
Relays and Sensors
Although multiple sensors and sensor types may be connected to the unit, there must always be
an
end of line (EOL) terminating resistor
at the end of the sensing circuit to allow for
cable break
monitoring
and
alarm reference set point
. The unit relies upon a terminating resistor of value
47k ohms
.
The unit should be
powered OFF
when making connections. Sensors should be installed so that they remain
accessible for maintenance
.
3.2.1
Relay Functions and Triggers
Relay Function
Description and Triggers
1-10
Individual zone
Used to operate auxiliary devices.
11
Common Alarm /
Fault
Relay latched upon alarm until acknowledged by User or Engineer.
✓
Zone cable break
✓
Motherboard communication
failure
✓
Zone Alarm
✓
Interface boards / communication
failure
12
Cable break
Relay latched upon alarm until acknowledged by User or Engineer.
✓
Zone cable break.
13
Alarm
Relay latched upon alarm until acknowledged by User or Engineer.
✓
Zone alarm
14
Latch on Alarm
(13) and/or Cable
Break (12).
Relay latched only when alarm or cable break present in real time.
✓
See Alarm (13) and/or Cable Break (12)
15
Watchdog
Relay normally energised. De-energised on any system fault.
✓
Motherboard loss of power
✓
Interface Board (IB) loss of power
✓
Complete power failure to EMS
✓
Motherboard communication
failure
✓
Interface Board communication
failure
16
Spare
Unused.
Not applicable
Table 3:
Relay Functions and Notes / Triggers