APtronic INV250-45 EU Quick Manual Download Page 1

turn over

- Mark the appropriate center of each PV module on the 

framework for inverter placement.

- Attach the Micro-Inverter using hardware accessories that are 

suitable for the framework used in the PV System, i.e. screws 

and sliding blocks. 

- Ensure a minimum distance of 20 mm between the roof top 

and the bottom of the inverter. In addition, a distance of 25 

mm between the back of the PV module and the top of the 

inverter should be complied with.

- Make a note of the serial numbers of each inverter and the 

corresponding PV module. It will help you later to create an 

overview of your PV system.

- Connect the PV module to the Micro-Inverter using the DC 

Cabling.

- Switch in the circuit breaker to energize the AC line.

1

2

3

This Quick Manual provides basic information for the installation of the APtronic 

Micro-Inverter. For detailed information, please refer to the Installation Manual 

provided on CD.

WARNING! 

All electrical installations must be done by in compliance with local and national 

electrical codes. 

CE Mark

The CE mark documents that according to the label the inverter fulfills the 

following essential requirements of relevant directives:

· Directive on the Electromagnetic Compatibility with the Directive 2004/108/EC 

 · Low Voltage Directive (Directive 2006/95/EC)

Accessories needed

1 - Mounting accessories for PV racking system

2 - Distribution Block

   - Cover for Distribution Block

3 - PV-modules including male and female connector Amhenol H4 

- The inverters are connected using 20A 3-pin AC extension 

cables and distribution blocks, with one input and three 

outputs, to form a continuous AC power circuit. 

- Make sure that the maximum number of inverters in a branch 

is not exceeded. (see table)

- Any unused AC Connectors must be covered with an end 

cap.       

- The end of the AC wire of one branch must be switched to  

a  circuit breaker with a current rating of 16A (20A) and a 

characteristic of type B. (see table)

QUICK MANUAL -INV-EU PLC

EU/50Hz/230V 

Installations:

16A Circuit Breaker

Non-EU/50Hz/230V 
Installations:

16A Circuit Breaker

Non-EU/50Hz/230V 
Installations:

20A Circuit Breaker

Type of inverter

Max. number of inverters in one branch

INV250-45 EU

12

12

15

INV350-60 EU

9

9

11

INV350-80 EU

9

9

11

INV500-80 EU

6

6

8

1

2

3