background image

WARNING

Hazardous voltage

can cause electrical shock and burns

Disconnect power before proceeding

with any work on this equipment

Cam Switch

LW39-16A

        EN60947-5-1

GB 14048.5

 Instructions

Before installing the device, please read the instructions.

 Summary

Main application

       LW39-16A switch is also used to control the start, brake,
       clockwise and anti-clockwise of small capacity motor and
       the speed governing of two-speed motor.

General product information

:

          Model specification

LW 39  - 16 A

 -

 -

······

 /

 -

 -

 -

 -

    

        

  

     

     

            

          

    

     

     

    

 Installation caution

     1)  We need to check whether the type meet selection requirement.
     2)  We must turn off power before installation and recondition.
     3)  Wiring refer to drawing and turn on the power after  you check
          carefully.
     4)  Choose the correct  operational voltage and current.
     5)  To prevent impurities metal powder into the product inside.
     6)  Tighten all terminal screws even if not used.
     7)  Don't open the parts with red mark.

 Technical feature

Parameters

     1) Rated  insulation voltage(Ui): 690 V.
     2)  Conventional thermal current(Ith): 16 A.
     3)  Power frequency withstand voltage : 1890 V / 5 s.

     4)  Mechanical life: 30 X 10

4

 times.

     5)  Electrical life : AC / 20 X 10

4

 times

DC / 10 X 10

4

 times

     6)  Type of fuse used in test of rated conditional short-circuit
          current

NT00-16A.

     7)  The ability of terminals wire:
        (1) The largest cross-section: 1.5mm². The maximum number
               of conductors connected to the terminal : 2.

        (2) The largest cross-section: 0.5mm². The maximum number
               of conductors connected to the terminal: 2.

        (3) Tightening torque: 0.8N·m.

    8) Usage category

DC-13

AC-15

Ie(A)

Ie(A)

Ue(V)

-

24 V

-

-

-

-

-

48 V 110 V

0.2 A

-

220 V

-

1.8 A

380 V

-

-

440 V

3

2017.1

Usage

category

Drawing No. : APT0.463.022.06

Operation condition

      1) Environment temperature : -25°C to +55°C
      2) Relative air humidity 

 90%

      3) Altitude

 2000 meters

      4) Installation category :

      5) Pollution class : 3

 The light box schematic diagram

1) Three terminals

[The common is anode]

-----default

2) Three terminals

[The common is cathode]

3) Four terminals

[There is no common, Intermediate is cathode]

4) Four terminals

[There is no common, Intermediate is anode]

       Note:Be careful to disassemble or assemble
                light box , to avoid damaging  them.

R

R

R

R

R

R

R

R

X1

X0

X0

X2

X1

X0

X2

R

R

R

R

X1

X0

X2

(+)

(-)

(-)

(-)

(+)

(+)

R

R

R

R

X1

X0

X0

X2

(-)

(-)

(+)

(+)

(+)

(+)

(-)

(-)

Siemens Electrical Apparatus Ltd., Suzhou, Tiantai Branch
Jigong Avenue 699- 10 Tiantai, Zhejiang,China
Sales Dept :Tsidi Building No.55,Lane 777,West Guangzhong Road Shanghai
Tel

021-56553757                http://www.china-apt.com

Switch type

Design number

Specification

Switch category

Function code

 ⑥

Operating characteristics of code

Relative of nodes or section code

Stages

Panel code

Illuminated code

Handle style

 ⑫

Auxiliary code

Reviews: