Figure 6-2: Battery Test Mode Static vs Dynamic Mode
6.10.1
Parameters for Static Mode
The following parameters can be configured for the static battery test function:
Value
Range
Description
I
0...Nominal value of I
Maximum discharge current in Ampere
P
0...Nominal value of P
Maximum discharge power in Watt
R
Min....max. nominal value of R
Maximum discharge resistance in Ω (can be deactivated --> “OFF”
6.10.2
Parameters for Dynamic Mode
The following parameters can be configured for the dynamic battery test function:
Value
Range
Description
I1
0...Nominal value of I
Upper resp. lower current setting for pulsed operation (the
higher value of both is automatically used as upper level)
I2
0...Nominal value of I
P
0...Nominal value of P
Maximum discharge power in Watt
t1
1 s ... 36000 s
t1 = Time for the upper level of the pulsed current (pulse)
t2 = Time for the lower level of the pulsed current (pause)
t2
1 s ... 36000 s
6.10.3
Other Battery Test Mode Parameters
These parameters are available in both modes, but the values are separate in both modes:
Parameter
Range
Description
Discharge voltage
0...Nominal value of U
Variable voltage threshold to make the test stop when
reached (is connected to the battery voltage on the DC
input of the load)
Discharge time
0...10 h
Maximum test time after which the test can stop
automatically
Discharge capacity
0...99999 Ah
Maximum capacity to consume from the battery after
which the test can stop automatically
Logging interval
100 ms - 1 s, 5 s, 10 s
Writing interval for USB logging