UNBOXING

•  When unboxing the detector you will find the unit and its mounting base.
•  This comes with pre-formed mounting holes to mount the detector base 

and a securing screw on the base to ensure there is no unwanted removal.

For more information, please refer to the user manual. Available on apollo-fire.co.uk 

IMPORTANT TO CONSIDER

When mounting a wireless device, a comprehensive radio survey 
should have been carried out to establish the location that provides
the best coverage and optimum reach. Taking into consideration the building 
structure and materials, the survey identifies the wireless infrastructure
required and product locations for optimum performance, identifying
any factor that could prevent radio integrity.

Avoid fixing or mounting the unit close to the following: 
• Equipment that utilises large electrical currents
• Large metal objects or structures 
• Fluorescent lighting fittings 
• Metal ceiling structures 
• IT cabling.

Keep 2 meters minimum spacing between other wireless equipment
in the area to avoid signal interference.

EN54 approved environmental temperature range is -10°C to +55°C

• Remove the detector’s dust cover, intended to protect 

the unit during shipping.

• Remove the detector from the base twisting

anticlockwise.

Remove the battery compartment cover on the base

on the detector.

• A plastic pop out tag is removable from the base 

to enable you to label the address of the detector, 

prior to fixing to the ceiling: pop out the device label tag 

from the base and insert it into the side.

• Screw the base to the ceiling using all fixing holes

and appropriate-sized screws.

1

3

2

4

MOUNTING STEPS

Proceed as follows to complete the device installation. 

5

6

Ensure the programming switch in the base of the detector

is in position ON.

Remove the batteries’ insulating tab ensuring

the batteries are kept in their lodgement.

MOUNTING

HOLES

REMOVABLE

TAG

UNLOCK

SWITCH 

ON

REMOVE 

INSULATING 

TAG

INSIDE THE BOX

• 1 x Heat Detector  

with mounting base

• 2 x CR123A batteries

• 1 x Quick start guide

• Locate the mounting holes and mark them using a pencil

on the desired surface you are drilling.

• Using a suitable-sized drill bit (6 mm) drill  the marked

screw points on your chosen surface.

• Ensure you use the correct fixings for the type of surface 

you are mounting to.

RW1000-400APO

REACH Heat Detector

QUICK START GUIDE

THE BOX

Product Part Number

Product Description

RW1000-400APO

REACH Heat Detector

Apollo Fire Detectors Ltd. 36 Brookside Road, Havant, Hampshire, United Kingdom, PO9 1JR
T: +44 (0)23 9244 2706 - E: techsales@apollo-fire.com - W: www.apollo-fire.co.uk

RW_QSG_DETECTOR_HEAT_REV_A.1

RW1000-400APO

Scan QR code

for full user manual

Reviews: