PP2379/2012/Issue 2/ 

Locally Powered Zone Monitor

FUNCTION

The Locally Powered Zone Monitor powers and controls the 
operation of a zone of up to 40 Orbis®or Series 65® Apollo 
fire detectors.

FEATURES

The Locally Powered Zone Monitor is set to return an 
analogue value of 16 when all detectors on the zone are 
in quiescent state and 64 when a detector changes to an 
alarm state. The Locally Powered Zone Monitor latches in 
the alarm state.

An analogue value of 4 is transmitted during open-or 
short-circuit faults.

The Locally Powered Zone Monitor is fitted with a 
bi-directional short circuit isolator and will be unaffected 
by loop short circuits on either the loop input or loop 
output. For further information on isolators please refer 
to PIN sheet PP2090, available on request.

ELECTRICAL CONSIDERATIONS

The Locally Powered Zone Monitor requires a separate 
power supply of 21–28V DC. A 3k

 end-of-line resistor is 

required. 

PROTOCOL COMPATIBILITY

The Locally Powered Zone Monitor operates only with 
control panels using Apollo XP95® or Discovery® protocol. 
Please check with your control panel manufacturer for full 
compatability.

MECHANICAL CONSTRUCTION

The Locally Powered Zone Monitor is supplied with a 
polycarbonate backbox for surface mounting.

Three LEDs, one green, one red and one yellow, are visible 
through the front cover of the enclosure

The green LED is illuminated to indicate that local power 
has been applied to the unit.

The red LED is illuminated to indicate that a detector on 
the zone has changed to the alarm state.

The yellow LED is illuminated whenever the isolator has 
sensed a short circuit loop fault.

Locally Powerered Zone Monitor
Part Number: 55000-864

DIMENSIONS AND WEIGHT

150mm X 90mm x 48mm 

230g

www.acornfiresecurity.com

www.acornfiresecurity.com