Intelligent Base Mounted IR

³

 Flame Detector, 

Installation & Maintenance Guide

General

The Intelligent Base Mounted Triple Infra-red (IR

3

) Flame Detector, part no 55000-024, is 

designed for use where open flaming fires may be expected. It is sensitive to low-frequency, 

flickering infra-red radiation emitted by flames during combustion. False alarms due to such 

factors as flickering sunlight are avoided by a combination of filters and signal processing 

techniques. This product is not compatable with the 45681-321 isolator base.

Response to flames

In quiescent condition, i.e., in the absence of a flame, the detector returns an analogue 

value of 25. When a flame is visible, the detector signals an alarm by increasing the ana-

logue value returned to 55, usually within 1.5 seconds. The analogue value may continue to 

rise until it reaches a pre-set maximum of 64.

In the alarm state the IR

³

 Flame Detector latches for 20 seconds, with the analogue value 

decreasing to 25 once the flame is no longer detected.

Electrical considerations

The IR

³ 

Flame Detector is loop powered and needs no external supply. It is connected to a 

control panel using either the XP95

®

 or Discovery

®

 protocol. A remote LED alarm indicator 

may be connected to the flame detector.

Sensor window contamination

It is important to keep the sensor window clean and checks should be carried out at 

regular intervals–determined locally according to the type and degree of contamination 

encountered–to ensure optimal performance of the flame detector. Although flames can 

be detected when the window is contaminated, there may be a reduction of sensitivity as 

shown in the table overleaf.

It is recommended that the IR³ Flame Detector be disabled when the window is being 

cleaned.

© Apollo Fire Detectors Limited 2010, 

36 Brookside Road, Havant, Hants, PO9 1JR, UK

Tel +44 (0) 23 9249 2412  Fax +44 (0) 23 9249 2754

www.apollo-fire.co.uk

Technical Data

 

Supply voltage  17–28V DC

 Protocol 

5-9V

 Quiescent current 

2.5mA

 Alarm current 

4.2mA

 Switch-on surge current 9mA (peak) for 85ms

 Power-up  time  4 seconds

 Remote output characteristics 

connects to positive through 4.5KΩ

  

(5mA Maximum)

 Fire alarm threshold Analogue value 55 returned after 10Hz flame

  

flicker for 1.5 seconds

 Operating range 25m for 0.1m² n-heptane fire

  

(EN54-10, Class 1)

  

 Operating temperature –40°C to +70°C (no condensation or icing)

 Storage temperature –40°C to +70°C

 Relative humidity 0-95% (no condensation)

 IP rating 

66

 Housing material white polycarbonate

  

V-0 rated to UL94

 Dimensions 100mm diameter

  40mm height, 48mm in base

 Weight 150g detector, 210g in base

Additional Equipment

Portable flame detector test unit 

Part no. 29600-226 

Adjusted Mounting Bracket  

Part no. 29600-458

PP2331/2010/Issue 4