The Ancillary Base Sounder is loop powered and controlled by the control panel using output bit '0' in the 
communication protocol. 

 

Protocol bit use

 

OUTPUT

 

BIT

 

FUNCTION

 

INPUT

 

BIT

 

FUNCTION

 

 

0 sounder 

continuous 

0 con

fi

 rmation of sounder continuous 

 

Troubleshooting

Before investigating individual units for faults, it is important to check the system wiring is fault free. Earth 
faults on data loops may cause communication errors.

Ancillary Base Sounder

Installation Guide

General

The Ancillary Base Sounder, part no. 45681-276, incorporates an XP95/Discovery base. The sounder 
may be connected only to control panels which use the XP95 digital protocol.

The Ancillary Base Sounder is controlled by the detector associated with it and does not have a separate 
address of its own.  It operates when the remote output of the associated detector is switched and 
may be used only in conjunction with control panels designed to be used with Ancillary sounders. The 
sounder will not operate unless an XP95 or Discovery detector is 

fi

 tted.

Notes:  

The Ancillary Base Sounder does not feature an alert tone and sounders can not be  

 

 synchronised.

 

The Ancillary Base Sounder is not suitable for outdoor use.

 Fault 

Finding

 

   

  

 

Problem Possible 

Cause

 

No response or missing 

Incorrect address setting

 

 

Incorrect loop wiring

 

 

Too many sounders between isolators

 

Sounder fails to operate 

Control panel has incorrect cause & effect programming

  

Detector 

not 

fi

 tted or faulty

39214-200/Issue 2