Aplisens APC-2000ALW User Manual Download Page 1

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

DTR.APC.APR.ALW.03

(ENG)

 

 
 

 

APLISENS 

 
 

MANUFACTURE OF PRESSURE TRANSMITTERS 

AND CONTROL INSTRUMENTS

 

 
 

 

 

USER’S MANUAL 

 
 

SMART PRESSURE TRANSMITTER 

type:

 APC-2000ALW 

 

SMART DIFFERENTIAL PRESSURE TRANSMITTER  

type: 

APR-2000ALW, APR-2200ALW, APR-2000GALW 

 

SMART LEVEL PROBE 

type:

 APR-2000YALW 

 

SMART LEVEL TRANSMITTER

 APC-2000ALW/L… 

 

SMART DENSITY TRANSMITTER 

APR-2200ALW/D 

 
 

Edition E6 

 
 
 
 
 
 

WARSAW MAY 2018

 

APLISENS S. A.   03-192 Warszawa,  ul. Morelowa 7 

tel. +48 22 814 07 77;   fax +48 22 814 07 78 

www.aplisens.pl,  e-mail:  [email protected] 

Summary of Contents for APC-2000ALW

Page 1: ...W SMART DIFFERENTIAL PRESSURE TRANSMITTER type APR 2000ALW APR 2200ALW APR 2000GALW SMART LEVEL PROBE type APR 2000YALW SMART LEVEL TRANSMITTER APC 2000ALW L SMART DENSITY TRANSMITTER APR 2200ALW D Edition E6 WARSAW MAY 2018 APLISENS S A 03 192 Warszawa ul Morelowa 7 tel 48 22 814 07 77 fax 48 22 814 07 78 www aplisens pl e mail aplisens aplisens pl ...

Page 2: ...ce should be configured appropriately for the purpose for which it is to be used Incorrect configuration may cause erroneous functioning leading to damage to the device or an accident In systems with pressure transmitters there exists in case of leakage a risk to personnel on the side where the medium is under pressure All safety and protection requirements must be observed during installation ope...

Page 3: ... CONSTRUCTION 36 6 2 ENCLOSURE OF TRANSMITTERS 36 7 PLACE OF INSTALLATION 37 7 1 GENERAL RECOMMENDATIONS 37 7 2 LOW AMBIENT TEMPERATURE 37 7 3 HIGH MEDIUM TEMPERATURE 37 7 4 ELECTROSTATIC RISKS 37 7 5 MECHANICAL VIBRATION SHOCKS CORROSIVE MEDIA 38 8 INSTALLATION AND MECHANICAL CONNECTIONS 38 8 1 APC INSTALLATION AND CONNECTIONS 38 8 2 APR INSTALLATION AND CONNECTIONS 39 8 3 APR 2000GALW INSTALLATI...

Page 4: ...ITH REMOTE DIAPHRAGM 62 FIG 13 EXAMPLE HOW TO INSTALL THE APR 2000ALW TRANSMITTER ON A VERTICAL OR HORIZONTAL PIPE 63 FIG 14 EXAMPLE HOW TO INSTALL THE APR 2000ALW TRANSMITTER WITH A VALVE MANIFOLD TO A 2 PIPE 63 FIG 15 APR 2200ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH TWO REMOTE DIAPHRAGM SEALS EXAMPLES 64 FIG 16 APR 2200ALW DIFFERENTIAL PRESSURE TRANSMITTER WITH DIRECT AND REMOTE DIAPHRAGM SEAL...

Page 5: ...te in areas where there is a risk of explosion in accordance with the rating of the explosion protection design Depending on type and device version the following markings are used 2 2 1 Category 1 2G and 1 2D Not applicable to APR 2000GALW XX I M2 Ex db ia I Mb version with enclosure 1 4401 316 II 1 2G Ex ia db IIC T6 T5 Ga Gb II 1 2D Ex ia t IIIC T85ºC T100ºC Da Db KDB 08 ATEX 224X marking T6 an...

Page 6: ...tructural metal parts or pipes which are connected to the equipotential bonding system transmitters do not require to be earthed 5 2 Transmitters should be supplied from DC electrical source with voltage max 55V from transformer feeders or other devices which have at least a strengthened isolation among primary and secondary windings in which don t appear voltage higher than 250V The duty of power...

Page 7: ... of the covers be lubricated with non acid vaseline Because of the transmitter damage possibility the ambient temperature should not be allowed to become higher than 80ºC even when there is no explosion risk 6 The electrical connection way of transmitter s series APC 2000ALW XX APR 2000ALW XX APR 2200ALW XX APR 2000GALW XX and APR 2000YALW XX in Exd version Fig 2 In case of transmitter calibration...

Page 8: ... Exd IIC dimension OS O A Baseefa 06 ATEX 0056X 501 421 HAWKE M20x1 5 Exd IIC dimension OS O A Baseefa 06 ATEX 0056X ICG 623 HAWKE M20x1 5 Exd IIC dimension OS O A Baseefa 06 ATEX 0058X 501 453 HAWKE M20x1 5 Exd IIC dimension OS O A Baseefa 06 ATEX 0056X 501 453 RAC HAWKE M20x1 5 Exd IIC dimension OS O A Baseefa 06 ATEX 0056X 501 453 Universal HAWKE M20x1 5 Exd IIC dimension OS O A Baseefa 06 ATEX...

Page 9: ...erate in areas where there is a risk of explosion in accordance with the rating of the explosion protection design Depending on type and device version the following markings are used 2 2 1 Equipment protection level EPL Ga Gb and Da Db Not applicable to APR 2000GALW XX Ex db ia I Mb version with enclosure 1 4401 316 Ex ia db IIC T6 T5 Ga Gb Ex ia t IIIC T85ºC T100ºC Da Db IECEx KDB 14 0001X marki...

Page 10: ... are connected to the equipotential bonding system transmitters do not require to be earthed 5 2 Transmitters should be supplied from DC electrical source with voltage max 55V from transformer feeders or other devices which have at least a strengthened isolation among primary and secondary windings in which don t appear voltage higher than 250V The duty of power supply installation with above ment...

Page 11: ...ed with non acid vaseline Because of the transmitter damage possibility the ambient temperature should not be allowed to become higher than 80ºC even when there is no explosion risk It is not permitted to repair or otherwise interfere with the transmitter s electrical circuits in any way Damage estimation and repair possibility may be assessed by the manufacturer or another authorized party only I...

Page 12: ...e should be made to DTR APC APR ALW 03 ENG in conjunction with Appendix Exi ATEX 2 Use of APC APR transmitters in danger zones 2 1 The transmitters are produced in accordance with the requirements of the following standards EN 60079 0 2012 A11 2013 EN 60079 11 2012 EN 50303 2000 2 2 The transmitters may operate in areas where there is a risk of explosion in accordance with the rating of the explos...

Page 13: ...ntrinsic safe certificates The parameters of their outputs to the danger zone should not exceed the limit power supply parameters for the below specified transmitters Note Pressure transmitters in version MID operate temperature range 25ºC Ta 55ºC Power supply parameters Ui Ii Pi and temperature class T see section 5 1 5 3 5 4 of Appendix Exi ATEX Note Power supply parameters Ui Ii Pi and temperat...

Page 14: ... characteristic is normally ib The transmitter powered from such a supply is also an Ex device with protection level ib Example of practical provision of power supply use a stabilized power supply with Uo 24V with protection level ib and current limited to Io 25mA 5 5 Input inductance and capacity Ci 2 5nF Li 18µH Ci 30nF Li 0 75mH for MID version 5 6 Supply voltage min 10 5VDC 5 7 Load resistance...

Page 15: ...s of transmitter with surge arrester marked on the plate Version SA do not meet the requirements of Section 10 3 of the EN 60079 11 500Vrms This must be taken into account when installing the equipment Under certain extreme circumstances in dust explosive atmospheres the device with painting of aluminium enclosure and with plastic tables and with elements of diaphragm seals covered by PTFE may sto...

Page 16: ...ansmitters During installation and use of Ex transmitters reference should be made to DTR APC APR ALW 03 ENG in conjunction with Appendix Exi IECEx 2 Use of APC APR transmitters in danger zones 2 1 The transmitters are produced in accordance with the requirements of the following standards IEC 60079 0 2011 ed 6 0 IEC 60079 11 2011 ed 6 0 2 2 The transmitters may operate in areas where there is a r...

Page 17: ...ation The transmitters should be powered via the associated power feeding and measurement devices provided with the relevant intrinsic safe certificates The parameters of their outputs to the danger zone should not exceed the limit power supply parameters for the below specified transmitters 5 1 For power supply with a linear output characteristic Ui 30V Ii 0 1A Pi 0 75W 40ºC Ta 80ºC and T5 Power ...

Page 18: ...dix Exi ATEX Special conditions for safe use Versions of transmitter with surge arrester marked on the plate Version SA do not meet the requirements of Section 10 3 of the IEC 60079 11 500Vrms This must be taken into account when installing the equipment Under certain extreme circumstances in dust explosive atmospheres the device with painting of aluminium enclosure and with plastic tables and wit...

Page 19: ...er type is given the type of connection to the pressure installation Units of pressure on the rating plate of bars and MPa are used interchangeably 3 APC 2000ALW transmitters in MID version Application 3 1 Pressure Transmitters Series APC 2000ALW version in accordance with EN 12405 1 2005 A2 2010 are provided for use in gas volume conversion devices of type 2 equipped with a backup electrical powe...

Page 20: ...le glands and plugs you should use components dedicated to Ex zones to ensure temperature resistance to fuel gas families 1 and 2 and the above degree of protection Can be used cable glands with sealants such as TPE s for example EX1100 20 110 AGRO 5 1 Transmitters environmental parameters in the MID version Products in this embodiment meets the following requirements criteria by EN 12405 1 2005 A...

Page 21: ... power and signal receiving terminals SIGNAL and SIGNAL of transmitter should be used with the polarization behavior to SIGNAL to SIGNAL Terminals TEST and TEST of transmitter in the metrological applications are not used The cable shield should be connected one sidedly to grounding the manufacturer recommends connect the shield to the converter installation grounding point The way of APC 2000ALW ...

Page 22: ...gs can be made as follows systemically by HART System activated by a configuration program Report 2 and protected by password spec MID locking done with local buttons on the transmitter with a local menu command MID_WP It is possible to set the measuring range form 10 100bar up to 10 70bar Measuring range 10 100bar of transmitters is setting standard but it can be lower up to 10 70bar at the user ...

Page 23: ...tructive during detachment or alternative used metal rated plates have one of the screws sealed to the casing Access spec MID locking protects against unauthorized interference to transmitters from a HART system APC 2000ALW series transmitter manufacturer is using with a plastic seal in its MID realization Change of the spec MID locking status ON or OFF is possible after removing of the manufactur...

Page 24: ...After starting Report 2 program read data from the transmitter Installation parameters and current parameters of the transmitter are recorded in the tabs of the Report 2 And so in Identification tab read the identity data of the transmitter Basic parameters tab check the measuring range pressure unit and time constant Process Variables tab check the current parameters of the transmitter measuring ...

Page 25: ... it using HART communication before target installation Connection method is described in the user s manual Read transmitter settings using pre installed software Raport 2 0 Steps for preparation of transmitter for operation in functional safety systems 1 Checking equipment and software versions Hardware version is shown in the CPU hardware revision tab while software version is given in the CPU s...

Page 26: ...y Low alarm irrespective of the above settings 4 User may select refreshing time of the converter ADC in the Filtration tab Do not set time to 32 ms for operation in functional safety loop because in this operation mode the converter will not proceed verification of the current output NOTE The transmitter should be protected against modification of its settings after making the above described and...

Page 27: ...00 00 00 7 Set Write protect to Blocked in the Write protection tab to prevent change of settings using HART communication Application will ask for a password enter it The transmitter should be installed and supplied as described in the supplied user s manual after configuration and protection using Raport 2 0 software NOTE It is forbidden to establish HART communication with the transmitter when ...

Page 28: ...e reference should be made to DTR APC APR ALW 03 ENG in conjunction with Appendix Exi ATEX or Appendix Exd ATEX 1 5 Additional data for APC 2000ALW APR 2000ALW APR 2200ALW APR 2000GALW APR 2200ALW D and APR 2000YALW transmitters in intrinsic safety Ex versions in accordance with IECEX certificate is contained in the appendix designed to DTR APC APR ALW 03 ENG Appendix Exi IECEx and in flame proof ...

Page 29: ...sing a HART RS232 or HART USB Converter and Aplisens Raport 2 configuration software 4 IDENTIFYING MARKS ORDERING PROCEDURE 4 1 Every transmitter carries a rating plate containing at least the following information CE mark manufacturer name transmitter type serial number pressure range static pressure limit output signal power supply voltage Version types and the method of specifying the desired p...

Page 30: ...nce in the Ro current loop must be lower than this value to ensure the minimum voltage on the terminals of the converter throughout the current loop operating range up to 22 5 mA with regard to HART alarms and communication The resistance necessary for communication HART min 240Ω The maximum values of Rmax permissible load resistance for the supply voltage of the power supply Usup V DC should be c...

Page 31: ...5MPa 4 0 160bar 0 16MPa 1 6bar 160kPa 100 1 450bar 45MPa 5 0 70bar 0 7MPa 0 7bar 70kPa 100 1 140bar 14MPa 6 0 25bar 0 2 5MPa 0 25bar 25kPa 100 1 50bar 5MPa 7 0 7bar 0 0 7MPa 0 07bar 7kPa 100 1 14bar 1 4MPa 8 1 7bar 100 700kPa 0 07bar 7kPa 114 1 14bar 1 4MPa 9 1 1 5bar 100 150kPa 0 12bar 12kPa 20 1 4bar 400kPa 10 0 2bar 0 200kPa 100mbar 10kPa 20 1 4bar 400kPa 11 0 1bar 0 100kPa 50mbar 5kPa 20 1 2ba...

Page 32: ...in the PED Pressure Directive versions are produced with a measurement range in the interval from 1bar to 400bar gage or from 0 to 400bar absolute with the overpressure up to PS 440bar APC 2000ALW pressure transmitters with the S Mazut seal pressure connection assembled with the PED version can be produced within the range 1bar to 100bar gage or within the 0 100bar absolute and the overpressure up...

Page 33: ... vertical spacing of sealsx1 04 mH2O 40bar 1 6 2 bar 1 5 mH2O 15m 20 vertical spacing of sealsx1 04 mH2O 40bar 1 6 16 bar 1bar 15m 16bar 40bar The maximum vertical diaphragm seal spacing shown in the table applies to level measurement ensuring that it is possible to set the zero point of the transmitter when the tank is empty For measurements of density or phase boundaries in the sugar and chemica...

Page 34: ...Accuracy 0 1 FSO for the APR 2200ALW The other parameters as given in the p 5 3 4 Sealing effect errors as given in the relevant diaphragm seal Catalogue Card concerning the distance seal NOTE The additional absolute zero error due to ambient temperature can be compensated by configuring the transmitter seals and capillaries in accordance with the recommendations on pages II 23 and II 24 Product C...

Page 35: ...ic damping 0 30 s 5 4 4 APR 2000GALW Construction materials M20x1 5 6x1 adapter brass Valve manifold 1 4404 316L Valve manifold adapter 1 4404 316L 1 4 NPT connector brass 1 4404 316L or galvanized St3S carbon steel Other materials as given in 5 1 2 for APR 5 4 5 APR 2000GALW Pressure Connectors The terminals fit adapted to Ø6x1 plastic tubes Valve manifold adapter or 1 4 NPT connector see p 8 3 a...

Page 36: ... 1 FSO 10ºC 0 4 FSO in the whole compensation range Thermal compensation range 25 100ºC 40 80ºC special version 5 6 4 APC 2000ALW L level transmitter Pressure Connectors SG 25 sensor SG 25S sensor SG 25C sensor SG 25S tytan sensor SG 16 sensor 5 6 5 APC 2000ALW L pressure transmitter Pressure range see p 5 2 1 Metrological parameters see p 5 6 3 Pressure connectors see p 5 2 5 5 7 APR 2200ALW D Me...

Page 37: ... Fast Transient Burst EN 61000 4 4 1kV Criterion A Electrical Slow Transient Surge EN 61000 4 5 1kV Criterion B 5 8 2 Electromagnetic Compatibility emission Criterion according to CISPR16 1 CISPR 16 2 class B Radiated Emission Distance from antenna 3m limits quasi peak 0 15 30MHz 80 52dBμV m 30 2000MHz 54dBμV m Conducted Emission limits quasi peak 0 01 0 150MHz 96 50dBμV m 0 150 0 350MHz 60 50dBμV...

Page 38: ...equipped with ground terminals internal and external The basic units of transmitter are measuring sensor in which pressure signal is converted into electric signal and electronic units transforming signal from measuring sensor into unified output signal 6 3 Main electronics plate with display Main plate electronics with display is placed in the casing of polycarbonate It is placed in bigger from t...

Page 39: ...t be suitably protected then an alternative mounting location should be sought 7 1 4 Attention should also be paid to possible installation faults which may lead to measurement errors such as connections which are not tight sediment blockage in lines which are too narrow gas bubbles in a liquid line or liquid column in a gas line etc 7 2 Low Ambient Temperature When the solidification point of the...

Page 40: ...g hot air For the small measurement ranges the reading can be affected by the transmitter position and by the impulse lines configuration or the way in which they are filled with liquid This error can be corrected using the zero setting function 8 1 APC Installation and connections 8 1 1 The APC transmitters can be mounted directly on the rigid impulse lines For used connectors as in Figures 5a 6a...

Page 41: ...tanks with access to medium from top of tank as Fig 19 and 10 2 9 Level probes should be installed in a vertical position 8 5 APC 2000ALW L Installation and connections APC 2000ALW L installed in places where liquid level is measurement in wells tanks reservoirs etc The transmitter sensor is immersed in measured medium The sensor can be hung on the power cable by using a Aplisens SG handle but esp...

Page 42: ...ing down in the direction of the gland 9 2 Electrical connections for APC APR The APC APR transmitters are to be connected as shown in Fig 2a 2d In APC APR transmitters a 240Ω resistor is permanently fitted in series in the transmitter s current circuit and blocked up with jumper between SIGNAL and TEST as shown in Fig 2a and 2b When the resistance in the current loop is lower than 240Ω it is nece...

Page 43: ...as features which enable metrological and identification parameters to be set and altered The configurable metrological parameters affecting the transmitter s output current include the following a unit in which the measured pressure is expressed on the display b upper end point of the set range c lower end point of the set range d time constant e type of characteristic curve linear or radical Par...

Page 44: ...the message ERR_L16 local configuration of the transmitter is switched off To its switching on is necessary to use KAP 3 Calibrator or PC see HART command 132 133 The buttons are signed with symbols After pressing by 4 seconds any of the buttons on the display will appear EXIT If you will confirm this message by pressing and holding button by 1 sec you will leave the local change of the MENU setti...

Page 45: ...E6 43 DTR APC APR ALW 03 ENG ...

Page 46: ...N_HG inches of mercury at a temperature of 68 Fahrenheit FT_H2O Foot of water a temperature of 68 Fahrenheit MM_H2O mm of water at a temperature of 68 Fahrenheit MM_HG mm of mercury at 0 C MBAR millibar G SQCM grams per square centimetres KG SQCM kilogram per square centimetres technical atmosphere KPA kilopascal TORR tor mm Hg ATM physical atmosphere M_H2O meter of water at 4ºC MPA Megapascal INH...

Page 47: ...itter has to have the included service of Local Menu as well as switched off protection before record These parameters modification is possible by using KAP 03 communicator Raport 2 program or software using library EDDL default setting Local Menu service switched on protection before record switched off ERR_L09 applied_process_too_high Error will ensue out when given parameter pressure will be to...

Page 48: ...s write the own unit name After activating user s mode the rescale value will be visible on display LCD3 information display During normal operation is designed for continuous display of the base unit or the user units In case of errors in the transmitter s work it displays an error number In manual mode the local change settings menu displays options of selecting the setting It also displays erro...

Page 49: ...he APR 2200ALW transmitters to measure the level density of liquid and phase boundary Configuration of the APR 2200ALW transmitters to measure the level of liquid in a tank Configuration of the APR 2200ALW transmitters to measure density of liquids KAP 03 ...

Page 50: ...E6 48 DTR APC APR ALW 03 ENG KAP 03 ...

Page 51: ...e flow measurements with the orifice plate It is important to proper placement of the transmitter depending on the type of measured medium otherwise it may negative impact on the measurement Mounting diagram for liquid and steam flow Mechanical installation On the flange of the tank Upper equalization hole Lower equalization hole Diaphragm seal unit ...

Page 52: ...using computer and Aplisens Raport 2 software according with p 10 2 4 or locally with transmitter buttons up to 1 only according to p 10 2 5 of the Manual For transmitters with software from 1 9 version the cutoff point setting means that when the pressure is increasing from 0 to set cutoff point n FS the output signal is zero 4mA but in the setting cutoff point and above its the transmitter outpu...

Page 53: ...off function will be implemented to 5 of set range with pressure increase and to 4 8 of set range with a pressure decrease 10 3 Alarms The alarms indicate exceeding the operating parameters of the transmitter maximum temperature pressure and failures of the electronic components You can see the diagnostic checklist of alarm statuses by using RAPORT 2 software after reading transmitter parameters I...

Page 54: ...RV Range 4 0 mA 20 0 mA with simple characteristics 4 20 mA Range 20 0 mA 4 0 mA with inverse characteristics 20 4 mA within the pressure or differential pressure measurement range below the lower range value LRV Range 3 9 mA 4 0 mA for Normal mode with simple characteristics 4 20 mA Range 3 8 mA 4 0 mA for Namur mode with simple characteristics 4 20 mA or Range 20 0 mA 20 5 mA for Normal mode wit...

Page 55: ...d method is the dissolving of sediment 11 3 2 Sometimes transmitters malfunction due to damage caused by overloading e g in case of Application of excessive pressure Freezing or solidification of the medium Action of a hard object such as a screwdriver on the diaphragm Usually in such cases the symptoms are such that the output current falls below 4mA or rises above 20mA and the transmitter fails ...

Page 56: ... ways to the measuring loop are presented at diagrams During increasing of resistance in the measure loop at making the good transmission is necessary to make sure that the tension falls at sum resistances in the loop don t lower minimum tension at transmitter terminals see p 5 1 1 Connection of the APC APR transmitter Connect as shown in Fig 2a If it is necessary to enable communication with the ...

Page 57: ... a communicator or converter to the transmitter s terminals make sure that the resistance Ro from the transmitter s terminals to the power supply source lies within the range of 240 1100 If so connect the communicator or converter to the terminals as shown in Fig 2b Fig 2b The link of transmitter and communicator or converter to SIGNAL SIGNAL transmitter terminals in case of the resistance in curr...

Page 58: ...ller than 240Ω Fig 2d The link of transmitter and communicator or converter to SIGNAL SIGNAL transmitter terminals in case of the resistance in current loop is smaller than 240Ω If Ro in current loop is lower than 240Ω is necessary to connect 240Ω resistor to current loop by remove jumper from SIGNAL and TEST terminals After communication jumper should came back at its place ...

Page 59: ...E6 57 DTR APC APR ALW 03 ENG Fig 3 APC 2000ALW smart pressure transmitter Fig 4 APC APR display rotation possibility configuration buttons ...

Page 60: ...t photo back lighting off jumper in circular position back lighting on 180o with 900 pitch unscrew the display cover and casing display screws Configuration buttons Move the electronic unit from transmitter casing take up the upper part of the casing with display from the catch and revolve its to left or to right to the display setting at needed position Rotation possibility 180º with 90º pitch Sc...

Page 61: ... M20x1 5 thread Fig 7 P type connector with M20x1 5 thread Fig 8 CM30x2 type connector with flush diaphragm with M30x2 thread i TOP Fig 6a M type connector with M20x1 5 thread Fig 6b Socket for M type connector Fig 7a P type connector with M20x1 5 thread Fig 7b Socket for P type connector Fig 8a CM30x2 type connector with flush diaphragm with M30x2 thread Fig 8b Socket for CM30x2 type connector Fi...

Page 62: ... G1 2A min 15 21 5 0 2 0 2 G1 2 2 5 2 5 90 G1 2 20 3 G1 2 0 5 15 min 10 5 21 5 0 2 1 25 Fig 9 Process connections G1 2 and G1 Fig 9c CG1 2 type connector with flush diaphragm with G1 2 thread Fig 9d Socket for CG1 2 type connector Order code Socket CG1 2 Fig 9e CG1 type connector with flush diaphragm with G1 thread Fig 9f Socket for CG1 type connector Order code Socket CG1 Fig 9a G1 2 type connect...

Page 63: ... 2000ALW differential pressure transmitter with C type vented covers Fig 11 APR 2000ALW differential pressure transmitter with a single direct diaphragm seal example S T type tube flanged diaphragm seal S P type flush flanged diaphragm seal ...

Page 64: ...t Mounting bracket 25 made by APLISENS for fitting differential pressure transmitters with P type connector on a 25 pipe see catalogue cards Fitting accessories Fig 12 Example how to install the APR 2200ALW transmitters with remote diaphragm ...

Page 65: ...tall the APR 2000ALW transmitter with a valve manifold to a 2 pipe Fastener C2 for fitting differential pressure transmitters with C type connection to a 2 pipe or to a wall see catalogue cards Fitting accessories Fastener C2 for fitting differential pressure transmitters with a valve manifold to a 2 pipe see catalogue cards Fitting accessories ...

Page 66: ...APC APR ALW 03 ENG Fig 15 APR 2200ALW differential pressure transmitter with two remote diaphragm seals examples Fig 16 APR 2200ALW differential pressure transmitter with direct and remote diaphragm seal examples ...

Page 67: ...E6 65 DTR APC APR ALW 03 ENG Fig 17 Example how to install the APC APR transmitter Fastening to a wall Fastening on a pipe ...

Page 68: ... 2000GALW transmitter industrial version with C type process connector to mount together with a valve manifold or weldable impulse line connectors b APR 2000GALW transmitter economical version with PCV type process connector c APR 2000GALW transmitter with GP or P type process connector G1 2 or M20x1 5 thread ...

Page 69: ...E6 67 DTR APC APR ALW 03 ENG Fig 19 APR 2000YALW smart level probe for pressure tanks ...

Page 70: ...explosion proof joints of APC APR transmitters CIRCUIT IS ALIVE FIELD TERMINALS WARNING Lock the cover tight by unbolting the screw K E EP COVER T IG H T W H E N C I R C U I T S A L I V E Fig 21 How to lead the casing of APC APR transmitters ...

Page 71: ...E6 69 DTR APC APR ALW 03 ENG Fig 22 APC 2000ALW LSG smart level transmitters ...

Page 72: ...E6 70 DTR APC APR ALW 03 ENG Fig 23 APC 2000ALW LM APC 2000ALW LSP smart pressure or level transmitters ...

Page 73: ...E6 71 DTR APC APR ALW 03 ENG Fig 24 APR 2200ALW D smart hydrostatic density transmitter example ...

Page 74: ...oint 5 2 5 E3 03 2017 Correction of norms Editorial corrections Added the figure to the 8th point of instruction E4 07 2017 The abs 1 7 MPa measuring range was added for the converters according to MID Editorial corrections in point 5 1 1 E5 01 2018 Information about the RoHS Directive has been added in p 1 E6 05 2018 Changes from actual catalog have been introduced ...