Potentiometer Input to DC Transmitters, Isolated, Field Rangeable
APD 4008
Input:
100
Ω to 1 MΩ Potentiometers, 0 to 90% Offset
Output:
0-1 V to ±10 VDC, or 0-2 mA to 20 mADC
O
One Minute Setup for Hundreds of I/O Ranges
O
External Switches & Table for Range Selection
O
Removable Plugs for Faster Installation
O
Full 1200 V Input/Output/Power Isolation
O
Input and Output LoopTracker
®
LEDs
O
Functional Output Test Button
O
Selectable Sink/Source for Current Output
Q
Over, Under, Out-of-Range Position Monitoring
Q
Remote Control of Positioning Devices
Q
Simplify Control of Potentiometer Outputs
Applications
Options–add to end of model number
DF
Fast response time, consult factory
U
Conformal coating for moisture resistance
Accessory—order as separate line item
API BP4
Spare 4-terminal plug, black
All models are field rangeable
Models can be pre-set to your specifications.
Order APD 4008 D for operation on low voltage power.
Model
Input
Output
Power
APD 4008
Field configurable—specify range if
factory is to set switches
Field configurable—specify range if
factory is to set switches
85-265 VAC, 50/60 Hz or
60-300 VDC
APD 4008 D
9-30 VDC or 10-32 VAC
Description
The APD 4008 accepts a resistance input from potentiometer,
slidewire, linear position, displacement, or rotational devices
and provides an optically isolated DC voltage or current output
that is linearly related to the potentiometer position.
The APD 4008 will accept any potentiometer with a value of
0-100
Ω
through 0-1 M
Ω
without recalibration and without
affecting accuracy. The APD 4008 output can be field-con-
figured via external rotary and slide switches. Offsets and/or
input ranges other than 0 to 100% of the potentiometer range
can also be selected.
The full 3-way (input, output, power) isolation makes this mod-
ule useful for ground loop elimination, common mode signal
rejection or noise pickup reduction.
Sink/Source Output
The APD 4008 has a 20 VDC loop excitation supply for the
output. This power supply can be used to power a passive mA
device. If not required, the APD 4008 output can be wired as
a passive output. Sinking/sourcing versatility allows the APD
4008 to produce a powered or unpowered mA output allowing
it to work with powered or unpowered mA devices.
LoopTracker
API exclusive features include two LoopTracker LEDs (green for
input, red for output) that vary in intensity with changes in the
process input and output signals. These provide a quick visual
picture of your process loop at all times and can greatly aid in
saving time during initial startup and/or troubleshooting.
Output Test
An API exclusive feature includes the test button to provide a
fixed output (independent of the input) when held depressed.
The test output level is potentiometer adjustable from 0 to
100% of output span.
The output test button greatly aids in saving time during initial
startup and/or troubleshooting.
How to Order
Please specify
Model
Input range (if factory is to pre-set)
Output range (if factory is to pre-set)
Options as required
Potentiometer Input
Field selectable ranges via switch settings
See table for complete listing
3 wire connection required
Minimum: 0-100
Ω
Maximum:
0-1 M
Ω
Input span:
10-100% of potentiometer range
Input offset:
0-90% in 10% increments
Input Impedance
10 M
Ω
minimum
Common Mode Rejection
120 dB minimum
LoopTracker
Variable brightness LEDs indicate I/O level and status
DC Output Ranges
Field selectable ranges via switch settings
See table for complete listing
Voltage:
0-1 VDC to 0-10 VDC, 10 mA max
Bipolar voltage: ±5 VDC or ±10 VDC
Current:
0-2 mADC to 0-20 mADC
20 V compliance, 1000
Ω
at 20 mA
Output Logic
Normal
Output Calibration
Multi-turn zero and span potentiometers
±15% of span adjustment range typical
Output Loop Power Supply
20 VDC nominal, regulated, 25 mADC, <10 mV
RMS
max. ripple
May be selectively wired for sinking or sourcing mA output
Output Test
Front button sets output to test level when pressed
Potentiometer adjustable 0-100% of span
Output Ripple and Noise
Less than 10 mV
RMS
Linearity
Better than ±0.1% of span
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than ±0.02% of span per °C stability
Response Time
Standard: 70 milliseconds nominal
DF option: 1 millisecond nominal. Output noise levels will be
greater than standard specifications. Consult factory.
Isolation
1200 V
RMS
minimum
Full isolation: power to input, power to output, input to output
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum
Removable Plugs
Dimensions
0.89" W x 4.62" H x 4.81" D
22.5 mm W x 117 mm H x 122 mm D
Height includes connectors
Universal
Power
Output LoopTracker
LED
Input LoopTracker
LED
Output Test
Function
Front Zero and Span
Connect mA Output
for Sink or Source
Use Any
Potentiometer
©
09-21
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
A
A
BSOLUTE
BSOLUTE
P
P
ROCESS
ROCESS
I
I
NSTRUMENTS
NSTRUMENTS
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
See Wiring
Diagrams on
Next Page
api-usa.com/4008
Minute
Setup!
1
Free Factory
I/O Setup!
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
File E145968
85-265 VAC, 60-300 VDC
model only
Applications Link