Aparton SPT-3B User Manual Download Page 1

USER’S

MANUAL

SPT-3B

HEAT DETECTORS

The detectors comply with EN 54-5:2000/A1:2002 A2R class.

The following abbreviations apply in the manual.
AL – alarm loop;
FACP – control panel.

1 PURPOSE

1.1 The SPT-3B heat detectors feature:
 - fixed temperature/rate-of-rise detection,
 - LED indication of standby mode,
 - remote reset,
 - 4-wire connection to 12V FACP or fire intruder CP,
 - indoor use.
1.2 Either when exceeding the threshold ambient temperature value the detector issues the alarm

signal for FACP or if the ambient temperature rate-of-rise is high even if the initial temperature much
lower than regular temperature of detector operation.

1.3 The Fire mode is indicated with the red LED indicator (steadily lit – DCAL, flashing– ACAL).
1.4 The red LED flashes every 1-2 sec in standby mode.

2 TECHNICAL SPECIFICATIONS

2.1 Static response temperature range, ° …………………………54 – 70
2.2 Supply voltage range, V………………………………………. 10 - 14
2.3 Standby current consumption, mA…………………………….  0,16
2.4 Alarm current consumption, m ………………………………22
2.5 Max relay contact current, mA…………………………………<100
2.6 Max relay contact voltage, V…………………………………..<36
2.7 N.C. relay contact resistance, Ohm…………………………….<5
2.8 N.O. relay contact resistance, kOhm….……………………….>500
2.9 Remote reset to standby mode, sec…………………………….3
2.10 Dimensions, mm.………………………………………………. 100 × 48
2.11 Weight, g ………………………………………………………150
2.12 Average lifespan, years ………………………………………... 10

3 ITEMS SUPPLIED WITH THE DETECTOR

Name

Quantity

Note

SPT-3B heat detector

Up to 25 pcs

B103-03 base included

Manual

1 pc.

Per a package

Package

1 pc.

Per 25 pcs